{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1336-7FP32","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1336-7FP32","canonicalUrl":"https://aoctrl.com/siemens/5SU1336-7FP32","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1336-7FP32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SU1336-7FP32, 3-pole, 32 A (30 °C), C-curve, 6 kA per EN 60898, 400 V AC, 50 Hz, IP20.","salesMarkdown":"The 5SU1336-7FP32: The 32 A rating at 30 °C is the headline figure, but the derating curve matters more for a warm enclosure: at 40 °C it carries 30.8 A, at 50 °C it drops to 29.5 A, and at 70 °C it is down to 26.9 A. If your panel ambient runs at 50 °C, size the load to 29.5 A continuous, not 32 A. For purely resistive loads with no inrush, a B-curve would be a tighter fit; for high-inrush transformers, a D-curve would be needed. Breaking capacity of 6 kA per both EN 60898 and IEC 60947-2 means it safely interrupts a 6 kA prospective fault current at 400 V AC — sufficient for most commercial and light industrial distribution boards fed by a transformer of typical impedance. The 500 V insulation voltage (Ui) and overvoltage category III confirm it is rated for fixed-installation mains distribution, not just final circuits. Depth is 72 mm, installation depth 70 mm — fits standard 80 mm deep enclosures. Mounting position is any, so horizontal or vertical orientation is fine as long as the distribution board is IP20 rated with conductors connected.","metaTitle":"Siemens 5SU1336-7FP32 SENTRON RCBO, 32 A, 6 kA, Type C, 3P","metaDescription":"Siemens 5SU1336-7FP32 SENTRON RCBO, 32 A rated at 30 °C, 6 kA breaking capacity per EN 60898, C-curve, 3-pole, 400 V AC, 50 Hz. Current production. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"72 mm","Width":"54 mm","Height":"85 mm","Maximum":"70 °C","Minimum":"-40 °C","Halogen-Free":"No","Design Of Pole":"3P","Number Of Poles":"3","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"400 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"3","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"375 g","at 30 °C rated value":"32 A","at 40 °C rated value":"30.8 A","at 45 °C rated value":"30.2 A","at 50 °C rated value":"29.5 A","at 55 °C rated value":"29.2 A","at 60 °C rated value":"28.2 A","at 70 °C rated value":"26.9 A","Energy Limitation Class":"1","For Testing Equipment Minimum":"340 V","Number Of Modular Width Units":"3","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"3","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"500 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"6 kA","Surge Current Resistance At (8/20) μS":"0.25 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/66546bef8d7957e3e6ae22e8a7f4e74b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1438050&mlfb=5SU1336-7FP32","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1336-7FP32/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the 5SU1336-7FP32?","answer":"It is rated 6 kA per both EN 60898 and IEC 60947-2 at 400 V AC, with a 4 kV surge voltage resistance."},{"question":"What is the temperature derating for this RCBO?","answer":"At 30 °C it is rated 32 A; at 40 °C it derates to 30.8 A, at 50 °C to 29.5 A, at 60 °C to 28.2 A, and at 70 °C to 26.9 A."},{"question":"Where can I buy the 5SU1336-7FP32?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation is available for the 5SU1336-7FP32?","answer":"The part carries EN 60898 and IEC 60947-2 ratings. Specific RoHS, REACH, and UL documentation should be confirmed at quote time against the manufacturer's current declarations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1336-7FP32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1336-7FP32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}