{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1353-1KK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1353-1KK06","canonicalUrl":"https://aoctrl.com/siemens/5SU1353-1KK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1353-1KK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 6 A, C-curve, 1P+N, 4.5 kA (EN 60898) / 25 kA (IEC 60947-2), 2 MW, halogen-free, silicon-free.","salesMarkdown":"## RCBO with C-curve — 6 A, 1P+N, 4.5/25 kA The Siemens 5SU1353-1KK06 is a SENTRON RCBO (residual current circuit breaker with overcurrent protection) rated 6 A at 30 °C with a C tripping characteristic, protecting a single-phase line (1P+N) at 230/240 V, 50 Hz. Breaking capacity is 4.5 kA per EN 60898 and 25 kA per IEC 60947-2. The 4.5 kA EN 60898 rating applies in a domestic or light-commercial distribution board. Either way, the device is energy-limiting class 3, so it restricts let-through energy on a short-circuit, protecting downstream wiring and connected loads. Rated 6 A at 30 °C ambient; derate to 5.7 A at 40 °C, 5.4 A at 50 °C, 5.1 A at 60 °C, and 4.62 A at 70 °C. In a crowded panel with internal temperature above 40 °C, the actual continuous load must stay under the derated value — the thermal-magnetic trip element responds to both current and ambient heat. The device occupies 2 modular width units (36 mm) on a 35 mm DIN rail, with a depth of 77 mm and installation depth of 70 mm. Supply can enter from either top or bottom — no mandatory line/load orientation.","metaTitle":"Siemens 5SU1353-1KK06 SENTRON RCBO, 6 A, C-curve, 1P+N, 4.5","metaDescription":"Siemens 5SU1353-1KK06 SENTRON RCBO, 6 A rated, C tripping characteristic, 1P+N, 4.5 kA per EN 60898, 25 kA per IEC 60947-2. Halogen-free, silicon-free. Current production. Quoted t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/abbaeb610608d20384ecbeb6a8f11b0d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=41796&mlfb=5SU1353-1KK06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1353-1KK06/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1353-1KK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1353-1KK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}