{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1353-7KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1353-7KK16","canonicalUrl":"https://aoctrl.com/siemens/5SU1353-7KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1353-7KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SU1353-7KK16, 1P+N, 16 A at 30 °C, tripping characteristic C, 4.5 kA per EN 60898, 2 MW, IP20.","salesMarkdown":"It protects a 1P+N final subcircuit at 230/240 V, 50 Hz, with a rated current of 16 A at 30 °C ambient and a Type C tripping characteristic (5–10× In for short-circuit and overload). The breaking capacity is 4.5 kA per EN 60898 and 15 kA per IEC 60947-2, giving it headroom for industrial panel coordination where the prospective fault current may exceed domestic levels. The 16 A rating at 30 °C is the headline figure, but the derating curve is what governs real-world panel placement. At 40 °C the continuous rating drops to 15.2 A; at 50 °C it is 14.4 A; at 60 °C it is 13.6 A; and at 70 °C it is 12.32 A. The Type C characteristic means the magnetic trip fires between 5 and 10 times the rated current (80–160 A for this 16 A unit). For purely resistive loads or long cable runs, Type B is a better selectivity match; for heavy motor starts, Type D may be needed. The 4.5 kA rating per EN 60898 covers the standard domestic/commercial fault level; the 15 kA per IEC 60947-2 matches industrial distribution boards with higher prospective short-circuit current. The energy limitation class is 3, meaning the device limits let-through energy to a low level, protecting downstream wiring and connected equipment. The 5SU1353-7KK16 snaps onto a 35 mm DIN rail per EN 60715, occupying 2 modular width units (36 mm). Installation depth is 70 mm; total depth including the housing is 77 mm.","metaTitle":"Siemens 5SU1353-7KK16 SENTRON RCBO, 16A, Type C, 4.5kA","metaDescription":"Siemens 5SU1353-7KK16 SENTRON RCBO, 1P+N, 16 A rated at 30 °C, tripping characteristic C, breaking capacity 4.5 kA per EN 60898. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5723c198aba5e0ab6e855d14d1102148.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=336085&mlfb=5SU1353-7KK16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1353-7KK16/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1353-7KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1353-7KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}