{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1353-7KL40","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1353-7KL40","canonicalUrl":"https://aoctrl.com/siemens/5SU1353-7KL40","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1353-7KL40","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1 RCBO, 1P+N, 40 A rated current, tripping characteristic C, 4.5 kA breaking capacity, type A fault current, halogen-free.","salesMarkdown":"The Siemens 5SU1353-7KL40 is a SENTRON 5SU1 RCBO (residual current circuit breaker with overcurrent protection) combining a 40 A rated current, type C tripping characteristic, and a 4.5 kA breaking capacity per EN 60898 into a single 1P+N unit. It detects type A fault currents — pulsating DC superimposed on AC — which covers most modern electronic loads like switched-mode power supplies and variable-speed drives. Above that, the device derates: 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, 32.4 A at 55 °C, 32.4 A at 60 °C, 30.8 A at 65 °C, and 29.2 A at 70 °C. If the panel ambient runs at 50 °C, the effective limit is 34.8 A — not 40 A. The type C magnetic trip (5–10× In) handles moderate inrush from motor starters and transformers without nuisance tripping, while the 4.5 kA SCCR at 230/400 V AC is adequate for most final subcircuits in a building distribution board. Overvoltage category III (distribution-level) and energy limiting class 3 mean it limits let-through energy enough to protect downstream wiring and loads under short-circuit conditions. The test button requires a minimum of 195 V to operate correctly — verify line voltage before commissioning. Accepts solid or stranded conductors from 0.75 mm² up to 35 mm² — enough for a 40 A circuit on 6–10 mm² copper. Supply can enter from either top or bottom, which simplifies busbar routing in a crowded enclosure. IP20 rated once the distribution board cover is installed and conductors are connected.","metaTitle":"Siemens 5SU1353-7KL40 SENTRON RCBO, 40 A, Type C, 4.5 kA","metaDescription":"Siemens 5SU1353-7KL40 SENTRON RCBO, 1P+N, 40 A rated, type C trip, 4.5 kA breaking capacity, type A fault current. Halogen-free. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-25 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f74268448af1a487a785ffaddf78e1bc.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=257211&mlfb=5SU1353-7KL40","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1353-7KL40/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1353-7KL40","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1353-7KL40 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}