{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1354-0KK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1354-0KK06","canonicalUrl":"https://aoctrl.com/siemens/5SU1354-0KK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1354-0KK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 1P+N, 6 A, B-curve, 30 mA Type AC, 10 kA (EN 60898), 35 kA (IEC 60947-2), 2 MW, 230/240 V AC.","salesMarkdown":"It protects a 1P+N final subcircuit at 6 A rated current, B-curve tripping characteristic, with 30 mA Type AC residual-current protection. That dual standard means it coordinates downstream of a larger upstream breaker without needing a current-limiting device in between. Mounts in any position. Rated IP20 once the distribution board is closed and conductors are connected; that's standard for a DIN-rail device inside a cabinet, not for an open panel. Halogen-free and silicon-free construction, which matters in clean-room or high-reliability environments where outgassing is a concern.","metaTitle":"Siemens 5SU1354-0KK06 SENTRON RCBO, 6A, B-Curve, 30mA, 10kA","metaDescription":"Siemens SENTRON 5SU1354-0KK06 RCBO, 1P+N, 6A, B-curve, 30mA Type AC, 10kA (EN 60898) / 35kA (IEC 60947-2). Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"277 g","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"1","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"35 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/79862f075697fa4089b848c674eda596.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=402408&mlfb=5SU1354-0KK06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1354-0KK06/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SU1354-0KK06?","answer":"10 kA per EN 60898 and 35 kA per IEC 60947-2. The higher figure under the industrial standard gives additional fault-current headroom for coordination studies."},{"question":"Will 5SU1354-0KK06 drop into a panel that was specified around 5SU9354-7KK16 without rewiring?","answer":"The 5SU9354-7KK16 is a C-curve variant with the same 2 MW footprint, 36 mm width, 77 mm depth, and 230/240 V AC rating. It will physically fit the same DIN-rail position and busbar arrangement. The functional difference is the tripping characteristic — B-curve (3-5× In) on the 5SU1354-0KK06 versus C-curve (5-10× In) on the peer — so check that the load's inrush profile matches the curve before swapping."},{"question":"Where can I buy 5SU1354-0KK06?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm commercial response."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1354-0KK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1354-0KK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}