{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1354-0LB13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1354-0LB13","canonicalUrl":"https://aoctrl.com/siemens/5SU1354-0LB13","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1354-0LB13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1 RCBO, 1P+N, 13 A rated current, B tripping characteristic, 10 kA breaking capacity per EN 60898, AC fault current type, 2 MW, IP20.","salesMarkdown":"The Siemens 5SU1354-0LB13 is a SENTRON RCBO — a combined residual-current and overcurrent protective device — in a 1P+N configuration, meaning it switches the line conductor and monitors the neutral for ground faults while providing overcurrent protection on the line side only. Above that, the device derates: 12.48 A at 40 °C, 12.22 A at 45 °C, 11.96 A at 50 °C, 11.57 A at 55 °C, 11.31 A at 60 °C, 10.53 A at 65 °C, and 10.01 A at 70 °C. The fault-current type is AC-only (senses sinusoidal residual currents). For pulsating DC or smooth DC fault currents, a type A or type B RCBO would be needed. Energy limiting class 3 indicates it lets through less let-through energy (I²t) than class 1 or 2 devices, reducing stress on downstream cables and components during a fault. It accepts solid or stranded conductors from 0.75 mm² up to 35 mm² — covering everything from 1.5 mm² lighting circuits to 10 mm² feeder tails. The supply can enter from either top or bottom, which simplifies busbar routing in a crowded distribution board. IP20 with the distribution board installed and conductors connected; the front face is finger-safe only when the board cover is closed. Mounting position is any — the device operates correctly upright, sideways, or inverted, which helps when the DIN rail is oriented vertically. The RCBO is designed to EN 60898 (the European standard for circuit-breakers for overcurrent protection in household and similar installations) and carries the CE marking. The device is classified per DIN EN 61346-2 and DIN EN 81346-2 as function code F (protective device). The minimum test voltage for the integral test circuit is 195 V AC — the test button will not operate correctly below that line voltage.","metaTitle":"Siemens 5SU1354-0LB13 SENTRON RCBO, 13 A, B Curve, 10 kA","metaDescription":"Siemens 5SU1354-0LB13 SENTRON RCBO, 1P+N, 13 A rated, B tripping characteristic, 10 kA breaking capacity per EN 60898. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Temp Operating Max":"55 °C","Temp Operating Min":"-25 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b11cb462b89584d26ac61679988d42ae.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=64076&mlfb=5SU1354-0LB13","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1354-0LB13/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1354-0LB13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1354-0LB13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}