{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1354-1RC25","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1354-1RC25","canonicalUrl":"https://aoctrl.com/siemens/5SU1354-1RC25","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1354-1RC25","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 25 A, 2-pole, 2-module, C characteristic, Type AC 30 mA, 10 kA per EN 60898, 20 kA per IEC 60947-2.","salesMarkdown":"The C characteristic means the magnetic trip fires at 5 to 10 times rated current — so for a 25 A RCBO, instantaneous trip occurs between 125 A and 250 A. That's the standard choice for motor-starter and lighting circuits where inrush is moderate; it avoids nuisance tripping on transformer or capacitor loads that a B-curve might catch. EN 60898 is the residential / commercial standard; the higher 20 kA rating under IEC 60947-2 means this RCBO is also rated for industrial distribution where fault currents can be stiffer. The 30 mA Type AC residual sensitivity catches sinusoidal AC earth faults — the standard for general-purpose socket-outlet and lighting circuits. It's not suitable for pulsating DC or smooth DC faults (those need Type A or Type F), so if the downstream load includes VFDs, UPS systems, or LED drivers, spec the A-type variant instead. IP20 with connected conductors is the norm for enclosed distribution boards — the RCBO itself isn't sealed against dust or moisture ingress, so it lives inside a cabinet rated for the environment. Mounts on standard DIN rail — any mounting position, supply feed from top or bottom. Depth is 70 mm, so it clears most 80 mm deep enclosures. That's the standard specification for fixed-installation distribution boards in residential and commercial settings.","metaTitle":"Siemens 5SU1354-1RC25 SENTRON RCBO, 25A, C-curve, 30mA, 10kA","metaDescription":"Siemens 5SU1354-1RC25 SENTRON RCBO, 25A rated, C characteristic, 30mA residual current, Type AC. 10kA per EN 60898, 20kA per IEC 60947-2. 2-pole, 2-module. Active production, avail","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2d80773e2de71436be68d97ddd68c249.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=440628&mlfb=5SU1354-1RC25","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1354-1RC25/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1354-1RC25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1354-1RC25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}