{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1354-4KK13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1354-4KK13","canonicalUrl":"https://aoctrl.com/siemens/5SU1354-4KK13","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1354-4KK13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1354-4KK13, RCBO, Type F, 13 A, C characteristic, 10 kA, 1P+N, 2 MW, halogen-free.","salesMarkdown":"The Siemens 5SU1354-4KK13 is a SENTRON RCBO combining a 13 A MCB with a Type F RCD in a 2-module-wide (36 mm) housing. Type F detects sinusoidal AC, pulsating DC, and mixed-frequency residual currents up to 1 kHz. ## Ratings that matter for the panel Power loss maxes at 4.4 W full-load, which keeps heat manageable in a packed enclosure. Ambient operating range is -25 to +55 °C, with a derating curve starting at 30 °C (13 A nominal) down to 10.01 A at 70 °C — useful when the RCBO sits near heat sources inside the panel. Mounts on standard DIN rail, any position.","metaTitle":"Siemens 5SU1354-4KK13 SENTRON RCBO, 13 A, Type F, 10 kA, 1P+","metaDescription":"Siemens SENTRON 5SU1354-4KK13 RCBO, 13 A rated, Type F fault current, 10 kA breaking capacity per EN 60898, 2 MW wide, halogen-free. Available to order; confirm pricing via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Solid":"0.75 ... 35 mm²","Width":"36 mm","Height":"90 mm","Maximum":"4.4 W","Stranded":"0.75 ... 35 mm²","at 30 Cel":"13 A","at 40 Cel":"12.48 A","at 45 Cel":"12.22 A","at 50 Cel":"11.96 A","at 55 Cel":"11.57 A","at 60 Cel":"11.31 A","at 65 Cel":"10.53 A","at 70 Cel":"10.01 A","Halogen-Free":"Yes","Silicon-Free":"Yes","During Storage":"-40 ... +75 °C","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-25 ... +55 °C","Product designation":"RCBO","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage category":"III","Energy limiting class":"3","Number of width units":"2","Type of fault current":"F","Number of poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SU1","Current / at AC / rated value":"13 A","Tripping characteristic class":"C","acc. to EN 60898 / rated value":"10 kA","For Testing Equipment / Minimum":"195 V","Position / of power supply cord":"Either top or bottom","Number of poles / with protection":"1","acc. to IEC 60947-2 / rated value":"20 kA","Product feature / Touch protection":"Yes","Supply voltage frequency / rated value":"50 Hz","Tripping residual current / rated value":"30 mA","Influence of the surrounding temperature":"Max. 95% humidity","Surge current resistance / at (8/20) μs":"3 kA","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Product function / neutral conductor switching":"Yes","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bad7e687161ffacaac3a7b5ea4d1e5d8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=366838&mlfb=5SU1354-4KK13","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1354-4KK13/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 5SU1354-4KK13?","answer":"The 5SL6563-7BB is a Siemens RCBO from the same SENTRON family but with different ratings — verify your required current, tripping characteristic, and fault type before substituting. The 5SU1354-4KK13 is Type F, 13 A, C-curve, 10 kA; the 5SL6563-7BB may differ in one or more of these parameters."},{"question":"What is the depth of 5SU1354-4KK13?","answer":"Overall depth is 77 mm; installation depth (behind the panel face) is 70 mm."},{"question":"What conductor cross-section does 5SU1354-4KK13 accept?","answer":"Solid and stranded conductors from 0.75 mm² up to 35 mm²."},{"question":"Will 5SU1354-4KK13 drop into a panel specified around 5SL6563-7BB without rewiring?","answer":"Both are 2-MW wide (36 mm) DIN-rail RCBOs from the same SENTRON family, so the mechanical fit is identical. However, verify the electrical ratings — the 5SU1354-4KK13 is Type F, 13 A, C-curve, 10 kA; the 5SL6563-7BB may have different values. No rewiring needed if the ratings match your circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1354-4KK13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1354-4KK13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}