{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1354-6GV16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1354-6GV16","canonicalUrl":"https://aoctrl.com/siemens/5SU1354-6GV16","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1354-6GV16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, B-curve, 16 A, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 1P+N, 2 MW, IP20, 77 x 36 x 90 mm.","salesMarkdown":"It combines a B-curve overcurrent trip at 16 A with an integrated residual current device in a single 1P+N pole configuration — one protected pole plus a switched neutral. ## B-curve and thermal derating At a 30 °C ambient the unit carries 16 A continuously; at 40 °C it derates to 15.2 A, at 50 °C to 14.4 A, and at 70 °C to 12.32 A. This thermal derating curve means the installer must account for enclosure heat rise when loading the circuit near the nominal rating, particularly in densely populated distribution boards. The housing measures 77 mm deep by 36 mm wide by 90 mm tall, occupying 2 modular-width units (MW) on a standard DIN rail. Installation depth is 70 mm. IP20 protection applies once the distribution board is installed with conductors connected — this is an enclosed-panel device, not rated for exposed or washdown environments.","metaTitle":"Siemens 5SU1354-6GV16 SENTRON RCBO, B-Curve 16 A, 10 kA, 2P","metaDescription":"Siemens 5SU1354-6GV16 SENTRON RCBO, B-curve 16 A, 10 kA per EN 60898, 20 kA per IEC 60947-2. 2-pole, 1P+N, 2 MW. Active production, sourced to order. RFQ for current pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"283 g","at 30 °C rated value":"16 A","at 40 °C rated value":"15.2 A","at 45 °C rated value":"14.88 A","at 50 °C rated value":"14.4 A","at 55 °C rated value":"13.92 A","at 60 °C rated value":"13.6 A","at 65 °C rated value":"12.96 A","at 70 °C rated value":"12.32 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"1","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"20 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4f3b99503a993c6f3e8f9501367738fb.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604369&mlfb=5SU1354-6GV16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1354-6GV16/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 5SU1354-6GV16 and what is the lead time?","answer":"The 5SU1354-6GV16 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quotation."},{"question":"What is the breaking capacity of the 5SU1354-6GV16?","answer":"The RCBO is rated 10 kA according to EN 60898 and 20 kA according to IEC 60947-2, covering the two common standards for final-circuit protection."},{"question":"What is the difference between the 5SU1354-6GV16 and the 5SL6516-6YA?","answer":"The 5SL6516-6YA is a Siemens SENTRON MCB (overcurrent only), while the 5SU1354-6GV16 is an RCBO combining overcurrent and residual-current protection in one unit. The 5SU1354-6GV16 cannot be replaced by a bare MCB when earth-fault protection is required."},{"question":"What compliance documentation is available for the 5SU1354-6GV16?","answer":"The unit is halogen-free and silicon-free. It carries a rated insulation voltage of 264 V, overvoltage category III, and pollution degree 2. The listed standards are EN 60898 and IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1354-6GV16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1354-6GV16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}