{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1354-7GV06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1354-7GV06","canonicalUrl":"https://aoctrl.com/siemens/5SU1354-7GV06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1354-7GV06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1 series RCBO, 2-pole 1P+N, 6 A rated, C tripping characteristic, Type A fault current, 10 kA (EN 60898) / 35 kA (IEC 60947-2), 2 width units.","salesMarkdown":"## Siemens 5SU1354-7GV06 RCBO — 6 A, Type A, C Curve The Siemens 5SU1354-7GV06 is a SENTRON RCBO combining overcurrent and residual current protection in a 2-pole 1P+N package. The Type A fault-current detection catches pulsating DC and sinusoidal AC earth faults — common in single-phase rectifier circuits or VFD-fed equipment. Breaking capacity is 10 kA per EN 60898 for domestic-style coordination, and 35 kA per IEC 60947-2 for industrial panel duty; that 35 kA rating means it can interrupt a high-fault bolted short without upstream fuses needing to clear first, which simplifies selectivity in a distribution board. ## Thermal derating and conductor sizing Above that, the thermal-magnetic trip derates: 5.7 A at 40 °C, 5.4 A at 50 °C, 5.1 A at 60 °C, and 4.62 A at 70 °C. If the panel runs warm — say 50 °C inside a sealed enclosure — the effective continuous current drops to 5.4 A, which matters when sizing the downstream load. The terminals accept 0.75 mm² to 25 mm² solid or stranded copper, so it lands on standard 2.5 mm² lighting circuits or 4 mm² small-power feeds without adapters. The 5SU1354-7GV06 snaps onto a DIN rail (2 width units, 36 mm wide) and fits any mounting position — horizontal, vertical, upside down — with an installation depth of 70 mm and overall depth of 77 mm. The supply cord can enter from the top or bottom, which simplifies busbar routing in a crowded distribution board. Touch protection is built in, so live terminals are shielded when the front cover is closed.","metaTitle":"Siemens 5SU1354-7GV06 SENTRON RCBO, 6 A, Type A, 10 kA","metaDescription":"Siemens 5SU1354-7GV06 SENTRON RCBO, 2-pole 1P+N, 6 A rated, C curve, Type A fault current, 10 kA (EN 60898) / 35 kA (IEC 60947-2). Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"25 mm²","Minimum":"0.75 mm²","at 30 Cel":"6 A","at 40 Cel":"5.7 A","at 45 Cel":"5.58 A","at 50 Cel":"5.4 A","at 55 Cel":"5.22 A","at 60 Cel":"5.1 A","at 65 Cel":"4.86 A","at 70 Cel":"4.62 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Product designation":"RCBO","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage category":"III","Design of the product":"Instantaneous","Energy limiting class":"3","Number of width units":"2","Type of fault current":"A","Number of poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SU1","Current / at AC / rated value":"6 A","Tripping characteristic class":"C","acc. to EN 60898 / rated value":"10 kA","For Testing Equipment / Minimum":"195 V","Position / of power supply cord":"Either top or bottom","Number of poles / with protection":"1","acc. to IEC 60947-2 / rated value":"35 kA","Product feature / Touch protection":"Yes","Supply voltage frequency / rated value":"50 Hz","Tripping residual current / rated value":"30 mA","Influence of the surrounding temperature":"Max. 95% humidity","Surge current resistance / at (8/20) μs":"1 kA","Product function / neutral conductor switching":"Yes","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b7ef1f591e4515069ae9ceff7ba4035f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1265700&mlfb=5SU1354-7GV06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1354-7GV06/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SU1354-7GV06?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What is the difference between 5SU1354-7GV06 and 5SL6563-7BB?","answer":"The 5SL6563-7BB is a Siemens SENTRON MCB (overcurrent only), while the 5SU1354-7GV06 is an RCBO that adds Type A residual-current protection. If the panel requires earth-fault protection on the same pole, the RCBO replaces both an MCB and an RCD in one module — but it will not drop into a slot wired for a plain MCB without adding the neutral connection."},{"question":"What is the depth of 5SU1354-7GV06?","answer":"Overall depth is 77 mm; installation depth (behind the panel face) is 70 mm."},{"question":"What is the width of 5SU1354-7GV06?","answer":"36 mm, which is 2 width units on a standard DIN-rail profile."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1354-7GV06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1354-7GV06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}