{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1354-7GV16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1354-7GV16","canonicalUrl":"https://aoctrl.com/siemens/5SU1354-7GV16","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1354-7GV16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1354-7GV16 RCBO, 1P+N, 16 A rated at 30 °C, C-curve, 10 kA per EN 60898 / 20 kA per IEC 60947-2, 30 mA type A residual current, halogen-free, silicon-free, IP20, 2 MW.","salesMarkdown":"It protects a single-phase final subcircuit (1P+N, neutral switched) against both overload/short-circuit and earth leakage. Rated 16 A at 30 °C ambient, with a published derating curve down to 12.32 A at 70 °C — important if the RCBO shares a crowded enclosure with other heat sources. In practice, the 20 kA figure governs when the RCBO is installed in an industrial panel with a higher prospective fault current. The 10 kA rating is the limit for residential or light-commercial boards. The 4 000 V surge voltage resistance (impulse withstand) and overvoltage category III rating confirm it is suitable for fixed-installation distribution boards, not just plug-in portable equipment. Mounts in any orientation — the evidence states 'any' mounting position. IP20 only when installed with connected conductors, so the RCBO itself is not rated for wet or dusty environments; the enclosure must provide the environmental seal. Listed as current production — no phase-out notice on record. The 5SU1354-7GV16 is a standard catalog item in the SENTRON range, not a special or end-of-life variant.","metaTitle":"Siemens 5SU1354-7GV16 SENTRON RCBO, 16 A C-Curve, 10/20 kA","metaDescription":"Siemens 5SU1354-7GV16 SENTRON RCBO, 1P+N, 16 A at 30 °C, C-curve, 10 kA per EN 60898 / 20 kA per IEC 60947-2. Halogen-free, silicon-free. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"282 g","at 30 °C rated value":"16 A","at 40 °C rated value":"15.2 A","at 45 °C rated value":"14.88 A","at 50 °C rated value":"14.4 A","at 55 °C rated value":"13.92 A","at 60 °C rated value":"13.6 A","at 65 °C rated value":"12.96 A","at 70 °C rated value":"12.32 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"20 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/70506afb237ad54785764330ef63bb6c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604371&mlfb=5SU1354-7GV16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1354-7GV16/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1354-7GV16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1354-7GV16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}