{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1354-7VK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1354-7VK10","canonicalUrl":"https://aoctrl.com/siemens/5SU1354-7VK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1354-7VK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1354-7VK10, RCBO, 2-pole, 10 A rated, 30 mA Type A residual current, tripping characteristic C, breaking capacity 10 kA per EN 60898 / 20 kA per IEC 60947-2, 2 MW units, IP20.","salesMarkdown":"## What this RCBO covers The Siemens 5SU1354-7VK10 is a 2-pole RCBO from the SENTRON Super Resistant K design, combining overcurrent protection (characteristic C) and residual current protection (Type A, 30 mA) in a single 36 mm wide unit. It's rated 10 A at AC, with a breaking capacity of 10 kA per EN 60898 and 20 kA per IEC 60947-2. The 30 mA trip threshold covers the standard personnel-protection requirement for socket circuits and wet-area final subcircuits. Type A detection handles pulsating DC fault currents from rectified loads — common in modern electronics, LED drivers, and variable-speed drives. ## Temperature derating and panel fit The 10 A rating holds at 30 °C ambient; it derates to 9.5 A at 40 °C, 9.3 A at 45 °C, 9 A at 50 °C, 8.7 A at 55 °C, and 8.5 A at 60 °C.","metaTitle":"Siemens 5SU1354-7VK10 SENTRON RCBO, 2-pole, 10 A, 30 mA, Typ","metaDescription":"Siemens 5SU1354-7VK10 SENTRON RCBO, 2-pole, 10 A rated, 30 mA Type A residual current, tripping characteristic C. Breaking capacity 10 kA (EN 60898) / 20 kA (IEC 60947-2). Active p","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Super resistant K","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"293 g","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.5 A","at 45 °C / rated value":"9.3 A","at 50 °C / rated value":"9 A","at 55 °C / rated value":"8.7 A","at 60 °C / rated value":"8.5 A","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"10 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"20 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"3 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$157.52","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=16179&mlfb=5SU1354-7VK10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1354-7VK10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SU1354-7VK10 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is 5SU1354-7VK10's listed depth?","answer":"The listed depth is 77 mm, with a 70 mm installation depth required in the panel."},{"question":"What is 5SU1354-7VK10's listed width?","answer":"The width is 36 mm, corresponding to 2 modular width units on a standard DIN rail."},{"question":"What compliance documentation does this brand provide for 5SU1354-7VK10?","answer":"The SENTRON series carries CE marking per the Low Voltage Directive and RoHS compliance as standard. Check the nameplate for specific UL or CSA listing on the unit received."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1354-7VK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1354-7VK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}