{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1354-7VK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1354-7VK16","canonicalUrl":"https://aoctrl.com/siemens/5SU1354-7VK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1354-7VK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1354-7VK16 RCBO, 2-pole, 16 A, Type A, 10 kA (EN 60898) / 20 kA (IEC 60947-2), 2 MW, C characteristic, halogen-free, IP20.","salesMarkdown":"This is the Super resistant K design, meaning the housing and internals are built for higher ambient temperatures and aggressive atmospheres — halogen-free and silicon-free, so it won't outgas or corrode sensitive contacts in sealed enclosures. The 16 A rating holds at 30 °C ambient, but drops to 15.2 A at 40 °C, 14.4 A at 50 °C, and 12.32 A at 70 °C. That 20 kA figure is the one to use for industrial panel SCCR calculations — it tells you the device can safely interrupt a 20 kA prospective fault current at 230/400 V without welding or exploding. ## Physical fit and mounting Width is 36 mm (2 modular units), depth 77 mm, height 90 mm, with an installation depth of 70 mm behind the panel face. The IP20 rating applies when installed in a distribution board with conductors connected; the device itself isn't rated for wet or dusty environments, so keep it inside the enclosure.","metaTitle":"Siemens 5SU1354-7VK16 SENTRON RCBO, 2-pole, 16 A, Type A, 10","metaDescription":"Siemens 5SU1354-7VK16 SENTRON RCBO, 2-pole, 16 A, Type A, 10 kA per EN 60898, 20 kA per IEC 60947-2. Current production. Quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","acc. to IEC 81346-2":"F","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Super resistant K","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"286 g","at 30 °C / rated value":"16 A","at 40 °C / rated value":"15.2 A","at 45 °C / rated value":"14.88 A","at 50 °C / rated value":"14.4 A","at 55 °C / rated value":"13.92 A","at 60 °C / rated value":"13.6 A","at 65 °C / rated value":"12.96 A","at 70 °C / rated value":"12.32 A","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"10 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"20 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"3 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=378534&mlfb=5SU1354-7VK16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1354-7VK16/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SU1354-7VK16?","answer":"10 kA per EN 60898 and 20 kA per IEC 60947-2. Use the 20 kA figure for industrial panel SCCR calculations."},{"question":"What is the thermal derating for this RCBO at elevated ambient temperatures?","answer":"Rated 16 A at 30 °C, derated to 15.2 A at 40 °C, 14.4 A at 50 °C, 13.6 A at 60 °C, and 12.32 A at 70 °C. Account for this if your panel runs hot."},{"question":"Where can I buy 5SU1354-7VK16 and how is it quoted?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability — no stock or lead-time figures are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1354-7VK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1354-7VK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}