{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1356-6GV16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1356-6GV16","canonicalUrl":"https://aoctrl.com/siemens/5SU1356-6GV16","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1356-6GV16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SU1356-6GV16, 2-pole 1P+N, 16 A rated, Type A, B-curve, 6 kA (EN 60898) / 15 kA (IEC 60947-2), IP20, 2 MW, 77 x 36 x 90 mm.","salesMarkdown":"The Siemens 5SU1356-6GV16 is a SENTRON RCBO (residual current operated circuit breaker with integral overcurrent protection) in a 2-pole 1P+N configuration. It combines a 16 A rated current with a Type A residual current detection and a B-curve tripping characteristic, so it protects both against overload and short-circuit as well as against sinusoidal AC and pulsating DC residual currents — common on circuits feeding single-phase rectifiers or electronics. The 16 A rating holds at 30 °C ambient; at 40 °C it derates to 15.2 A, at 50 °C to 14.4 A, and at 70 °C to 12.32 A. ## Installation and compliance notes Halogen-free and silicon-free construction supports use in clean-room or sensitive electronics environments where outgassing must be minimized. Designated as instantaneous (no intentional time delay on the residual current element), so it trips within the standard Type A response window.","metaTitle":"Siemens 5SU1356-6GV16 SENTRON RCBO, 2-pole 16A Type A, 6kA/1","metaDescription":"Siemens 5SU1356-6GV16 SENTRON RCBO, 2-pole 1P+N, 16 A rated, Type A residual current, B-curve, 6 kA (EN 60898) / 15 kA (IEC 60947-2). Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","acc. to IEC 81346-2":"F","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"276 g","at 30 °C / rated value":"16 A","at 40 °C / rated value":"15.2 A","at 45 °C / rated value":"14.88 A","at 50 °C / rated value":"14.4 A","at 55 °C / rated value":"13.92 A","at 60 °C / rated value":"13.6 A","at 65 °C / rated value":"12.96 A","at 70 °C / rated value":"12.32 A","Number Of Modular Width Units":"2","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"15 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c938ee0771dc4e3c8e1afdf3f8192191.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604374&mlfb=5SU1356-6GV16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1356-6GV16/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SU1356-6GV16?","answer":"Current pricing and availability are confirmed at quote time against an RFQ through our independent distribution network — submit a request and we'll return a firm quote with lead time."},{"question":"Will 5SU1356-6GV16 drop into a panel specified around 5SL6516-6YA without rewiring?","answer":"No — the 5SU1356-6GV16 is a 2-pole 1P+N RCBO (combined overcurrent and residual current protection), while the 5SL6516-6YA is a single-pole MCB only. They serve different functions and are not drop-in interchangeable; rewiring and possibly a different enclosure layout would be required."},{"question":"What compliance documentation does Siemens provide for 5SU1356-6GV16?","answer":"The part carries EN 60898 and IEC 60947-2 ratings, is halogen-free and silicon-free, and is designed to IEC 81346-2 and DIN EN 61346-2 functional standards. Specific RoHS/REACH declarations and UL listing status should be confirmed from the manufacturer's documentation at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1356-6GV16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1356-6GV16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}