{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1454-1KK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1454-1KK10","canonicalUrl":"https://aoctrl.com/siemens/5SU1454-1KK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1454-1KK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1454-1KK10 RCBO, 2-pole 1P+N, 10 A rated, 100 mA residual current, Type C tripping characteristic, 10 kA (EN 60898) / 20 kA (IEC 60947-2).","salesMarkdown":"Rated 10 A with a Type C tripping characteristic. Residual-current element is Type AC, 100 mA sensitivity. The 20 kA figure gives headroom for high-fault installations — a 10 kA board with a 20 kA device means the RCBO clears a fault before the upstream main breaker sees it, preserving selectivity. Energy limitation class 3 means it lets through less energy than a class-1 or class-2 device, reducing arc-flash risk and thermal stress on downstream wiring. Neutral conductor is switched internally (1P+N), so the neutral pole opens with the line pole, meeting disconnection requirements for single-phase circuits.","metaTitle":"Siemens 5SU1454-1KK10 SENTRON RCBO, 10 A, 100 mA, Type C, 10","metaDescription":"Siemens 5SU1454-1KK10 SENTRON RCBO, 2-pole 1P+N, 10 A rated, 100 mA residual, Type C, 10 kA (EN 60898) / 20 kA (IEC 60947-2). Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a066bfaf173237b28cdc013630c21750.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=158935&mlfb=5SU1454-1KK10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1454-1KK10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1454-1KK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1454-1KK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}