{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1454-1KK13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1454-1KK13","canonicalUrl":"https://aoctrl.com/siemens/5SU1454-1KK13","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1454-1KK13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1454-1KK13 RCBO, 2-pole (1P+N), Type C, 13 A at 30 °C, 10 kA per EN 60898, 20 kA per IEC 60947-2, 2 MW, halogen-free, IP20 with board installed.","salesMarkdown":"It combines a Type C miniature circuit breaker and a residual current device (Type AC) into one unit, protecting against both overload/short-circuit and earth leakage in a single 1P+N pole configuration. The breaking capacity is 10 kA per EN 60898 and 20 kA per IEC 60947-2, so it can interrupt fault currents up to 20 kA at 230/240 V AC without upstream cascading. ## Temperature derating and installation At 40 °C the continuous current drops to 12.48 A, at 55 °C to 11.57 A, and at 70 °C to 10.01 A. If the panel runs hot (e.g., enclosed with other heat-generating devices), use the derated figure for the BOM load calculation — the breaker will trip earlier than the nameplate suggests if the ambient exceeds 30 °C. IP20 is achieved only when the distribution board is installed with connected conductors — not a standalone rating. Halogen-free and silicon-free construction. Rated for 50 Hz only. The function designation per IEC 81346-2 and DIN EN 61346-2 is F. Test equipment minimum voltage is 100 V AC.","metaTitle":"Siemens 5SU1454-1KK13 SENTRON RCBO, 13 A, 10 kA, Type C, 1P+","metaDescription":"Siemens 5SU1454-1KK13 SENTRON RCBO, 13 A rated at 30 °C, 10 kA breaking capacity per EN 60898, Type C, 1P+N, 2 MW, halogen-free. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","at 30 Cel":"13 A","at 40 Cel":"12.48 A","at 45 Cel":"12.22 A","at 55 Cel":"11.57 A","at 60 Cel":"11.31 A","at 65 Cel":"10.53 A","at 70 Cel":"10.01 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","Type Of Voltage":"AC","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","acc. to IEC 81346-2":"F","at AC / rated value":"230/240 V","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"282 g","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"10 kA","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"20 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"100 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","operational current / at AC / rated value":"13 A","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=220283&mlfb=5SU1454-1KK13","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1454-1KK13/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SU1454-1KK13?","answer":"The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is 5SU1454-1KK13's listed depth?","answer":"The overall depth is 77 mm; the installation depth (behind the panel face) is 70 mm."},{"question":"What compliance documentation does this RCBO provide?","answer":"It is halogen-free and silicon-free, rated for overvoltage category III, pollution degree 2, and energy limitation class 3. The breaking capacity is certified per EN 60898 (10 kA) and IEC 60947-2 (20 kA)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1454-1KK13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1454-1KK13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}