{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1653-1KK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1653-1KK10","canonicalUrl":"https://aoctrl.com/siemens/5SU1653-1KK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1653-1KK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SU1653-1KK10, 1P+N, 10 A rated at 30 °C, tripping characteristic C, breaking capacity 4.5 kA per EN 60898, 2 modular width units.","salesMarkdown":"It occupies 2 modular width units (36 mm) on a DIN rail and is designed for 50 Hz supply systems at 230/240 V AC. The unit is halogen-free and silicon-free, suitable for environments with strict material restrictions. The breaking capacity is rated 4.5 kA per EN 60898 and 15 kA per IEC 60947-2 — the higher IEC figure applies when the device is used as a distribution board component with upstream current limitation. Energy limitation class 3 means it restricts let-through energy during a fault, helping downstream coordination. Mounts on a DIN rail in any orientation (mounting position any). The supply can enter from either the top or bottom, simplifying panel wiring. Thermal derating is specified from 30 °C upward: 10 A at 30 °C, 9.5 A at 40 °C, 9.3 A at 45 °C, 9 A at 50 °C, 8.7 A at 55 °C, 8.5 A at 60 °C, 8.2 A at 65 °C, and 8 A at 70 °C. The test circuit requires a minimum of 100 V for functional testing. Surge voltage withstand is 4 kV, insulation voltage 264 V.","metaTitle":"Siemens 5SU1653-1KK10 SENTRON RCBO, 10 A, Type C, 4.5 kA","metaDescription":"Siemens 5SU1653-1KK10 SENTRON RCBO, 1P+N, 10 A rated at 30 °C, tripping characteristic C, breaking capacity 4.5 kA per EN 60898. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","title":"5SU1653-1KK10","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, 4.5 kA, 1P+N, Type AC, 300 mA, C-Char, In: 10 A, Un AC: 230 V","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"268 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.5 A","at 45 °C rated value":"9.3 A","at 50 °C rated value":"9 A","at 55 °C rated value":"8.7 A","at 60 °C rated value":"8.5 A","at 65 °C rated value":"8.2 A","at 70 °C rated value":"8 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"100 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"4.5 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"15 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ec3c0caba76901685737c2d36fdc7664.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=214508&mlfb=5SU1653-1KK10"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SU1653-1KK10?","answer":"It is rated 4.5 kA according to EN 60898 and 15 kA according to IEC 60947-2."},{"question":"What is the width of 5SU1653-1KK10 in modular units?","answer":"It occupies 2 modular width units, which is 36 mm."},{"question":"Where can I buy 5SU1653-1KK10?","answer":"This RCBO is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1653-1KK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1653-1KK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}