{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1653-7KK13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1653-7KK13","canonicalUrl":"https://aoctrl.com/siemens/5SU1653-7KK13","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1653-7KK13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1653-7KK13 RCBO, 2-pole 1P+N, 13 A rated, Type A residual current, 30 mA sensitivity, tripping characteristic C, breaking capacity 4.5 kA (EN 60898) / 15 kA (IEC 60947-2), 2 MW width, halogen-free, silicon-free.","salesMarkdown":"It protects a single-phase final subcircuit against both overload/short-circuit and earth leakage, with a 13 A rated current and a Type A residual-current trip sensitive to 30 mA. Breaking capacity is rated at 4.5 kA per EN 60898 and 15 kA per IEC 60947-2. The higher IEC figure applies when the device is used as a circuit breaker in an industrial panel; the EN figure governs domestic/commercial final circuits. Either way, it handles typical fault levels on a 230/400 V TN system. Mounting position is any — no restriction on upright or horizontal orientation. Supply can enter from either top or bottom — no fixed line/load orientation. The 1P+N pole arrangement switches the phase and disconnects the neutral; the neutral pole is switched but not protected against overload. IP20 protection applies when installed in a distribution board with connected conductors — normal for enclosed panel use. ## Thermal derating and ambient range Derate to 12.48 A at 40 °C, 12.22 A at 45 °C, 11.96 A at 50 °C, 11.57 A at 55 °C, 11.31 A at 60 °C, 10.53 A at 65 °C, and 10.01 A at 70 °C. The wide low end covers unheated enclosures in cold climates; the high end accommodates panels near process heat. Halogen-free and silicon-free construction suits installations with strict material-compatibility requirements, such as rail, marine, or data-center environments.","metaTitle":"Siemens 5SU1653-7KK13 SENTRON RCBO, 13 A, Type A, 30 mA, 2 M","metaDescription":"Siemens 5SU1653-7KK13 SENTRON RCBO, 13 A rated, Type A residual current, 30 mA sensitivity, 2-pole 1P+N, tripping characteristic C. Breaking capacity 4.5 kA per EN 60898, 15 kA per","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/95b7755aef649c34a34d31e9125d0bee.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=66494&mlfb=5SU1653-7KK13","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1653-7KK13/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1653-7KK13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1653-7KK13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}