{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1654-1KK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1654-1KK10","canonicalUrl":"https://aoctrl.com/siemens/5SU1654-1KK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1654-1KK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1654-1KK10 RCBO, 1P+N, 10 A rated, 10 kA breaking capacity, 300 mA residual current, C-curve, instantaneous design, 2 MW width.","salesMarkdown":"The residual-current element is type AC, tripping at 300 mA — sized for general socket-outlet or sub-distribution protection where a lower 30 mA threshold isn't required. ## Fit and panel integration Depth is 77 mm, installation depth 70 mm — it fits flush in most residential or light-commercial distribution boards without protruding past the gland plate. Rated IP20 with the distribution board installed and conductors connected, so it's strictly indoor panel use — no washdown or outdoor exposure. ## Temperature derating — what the numbers mean Above that, the continuous current must be reduced: 9.5 A at 40 °C, down to 8 A at 70 °C.","metaTitle":"Siemens 5SU1654-1KK10 SENTRON RCBO, 10 A, 10 kA, 300 mA, C-c","metaDescription":"Siemens 5SU1654-1KK10 SENTRON RCBO, 10 A rated, 10 kA breaking capacity per EN 60898, 300 mA residual current, C-curve, 2-module width. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","at AC / rated value":"10 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Energy Limitation Class":"3","Weight / With Packaging":"272 g","according to EN 61346-2":"F","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.5 A","at 45 °C / rated value":"9.3 A","at 50 °C / rated value":"9 A","at 55 °C / rated value":"8.7 A","at 60 °C / rated value":"8.5 A","at 65 °C / rated value":"8.2 A","at 70 °C / rated value":"8 A","according to IEC 81346-2":"F","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","according to EN 60898 / rated value":"10 kA","Tripping Fault Current / Rated Value":"300 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","according to IEC 60947-2 / rated value":"20 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cd2d1a0a412b3b09179ac93f20d7d7b2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=91238&mlfb=5SU1654-1KK10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1654-1KK10/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SU1654-1KK10?","answer":"The rated breaking capacity is 10 kA according to EN 60898, which covers most residential and light-commercial fault levels."},{"question":"What residual current does 5SU1654-1KK10 trip at?","answer":"It trips at 300 mA rated residual current, type AC — suitable for general protection where a lower 30 mA sensitivity isn't needed."},{"question":"Where can I buy 5SU1654-1KK10?","answer":"This part is sourced and quoted to order through independent distribution against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is the width of 5SU1654-1KK10?","answer":"It is 36 mm wide, occupying 2 modular width units on standard DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1654-1KK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1654-1KK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}