{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1654-6KK32","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1654-6KK32","canonicalUrl":"https://aoctrl.com/siemens/5SU1654-6KK32","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1654-6KK32","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1654-6KK32 RCBO, 2-pole (1P+N), 32 A rated, Type A residual current, B-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2).","salesMarkdown":"It protects a single-phase final subcircuit against earth leakage (Type A, sensitive to pulsating DC fault currents) and overcurrent/short-circuit (B-curve magnetic trip). The 32 A rating at 30 °C is the headline figure; derate to 30.4 A at 40 °C and 24.64 A at 70 °C, so the continuous load must be sized against the installed ambient, not the nameplate. Width of 36 mm (2 modular units) fits standard DIN-rail enclosures. Mounting position is unrestricted — install upright, sideways, or inverted without derating. Supply cord entry can be from the top or bottom, simplifying busbar routing in a distribution board. Rated for overvoltage category III (fixed-installation level) and pollution degree 2. IP20 protection applies when the distribution board is installed with conductors connected — the device itself is not rated for exposed or washdown environments.","metaTitle":"Siemens 5SU1654-6KK32 SENTRON RCBO, 2-pole 32 A Type A, 10 k","metaDescription":"Siemens SENTRON 5SU1654-6KK32 RCBO, 2-pole (1P+N), 32 A rated, Type A residual current, B-curve, 10 kA (EN 60898) / 15 kA (IEC 60947-2). Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","acc. to IEC 81346-2":"F","at AC / rated value":"32 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"284 g","at 30 °C / rated value":"32 A","at 40 °C / rated value":"30.4 A","at 45 °C / rated value":"29.76 A","at 50 °C / rated value":"28.8 A","at 55 °C / rated value":"27.84 A","at 60 °C / rated value":"27.2 A","at 65 °C / rated value":"25.92 A","at 70 °C / rated value":"24.64 A","Number Of Modular Width Units":"2","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"10 kA","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"15 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"300 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5fdfc311129720c82ab7140b076e9f10.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=341644&mlfb=5SU1654-6KK32","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1654-6KK32/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SU1654-6KK32 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time."},{"question":"Will 5SU1654-6KK32 drop into a panel specified around 5SU9304-1KK32 without rewiring?","answer":"Both are 2-module-width (36 mm) RCBOs with 1P+N pole configuration, so the physical footprint and busbar pitch are the same. However, the 5SU9304-1KK32 carries different ratings — verify the rated current, tripping characteristic, and residual current type against your circuit design before substituting."},{"question":"What breaking capacity does 5SU1654-6KK32 have?","answer":"10 kA per EN 60898 for residential/commercial final circuits, and 15 kA per IEC 60947-2 for industrial distribution applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1654-6KK32","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1654-6KK32 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}