{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1656-0KK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1656-0KK06","canonicalUrl":"https://aoctrl.com/siemens/5SU1656-0KK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1656-0KK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2-pole 1P+N, 6 A rated, B-curve, AC residual current type, 30 mA sensitivity, 6 kA breaking capacity per EN 60898, 25 kA per IEC 60947-2, 2 MW wide, IP20, current production.","salesMarkdown":"The Siemens 5SU1656-0KK06 is a SENTRON RCBO — a combined residual-current and overcurrent protective device — in a 2-pole 1P+N configuration. It switches the line conductor only, with the neutral passing through the residual-current transformer but not switched. Rated 6 A at 30 °C with a clear thermal derating curve: 5.7 A at 40 °C, 5.4 A at 50 °C, 5.1 A at 60 °C, and 4.62 A at 70 °C. For a panel running at 50 °C ambient, the usable current is 5.4 A — not 6 A. The higher 25 kA figure applies when the device is certified under the industrial standard, giving headroom for high-fault locations like substation secondaries. Mounting position is any orientation. Supply can enter from top or bottom — no mandated orientation. The IP20 rating applies only when the distribution board is installed with connected conductors; the device itself is not sealed against dust ingress without the enclosure. The degree of pollution is 2 (non-conductive pollution that becomes conductive only when condensation occurs), typical for standard indoor distribution boards. Two modular-width units (36 mm) means it occupies the same slot pitch as two single-pole MCBs. The test button requires a minimum 100 V to operate the test circuit — verify the phase-to-neutral voltage exceeds this before relying on the built-in test function during commissioning. The product designation per IEC 81346-2 is F (protective device).","metaTitle":"Siemens 5SU1656-0KK06 SENTRON RCBO, 2-pole 6A B-curve 30mA","metaDescription":"Siemens SENTRON 5SU1656-0KK06 RCBO, 2-pole 1P+N, 6A B-curve, 30mA AC type, 6kA (EN 60898). Current production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d410a641b98c209d1cb9cb425a7a4a52.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=152020&mlfb=5SU1656-0KK06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1656-0KK06/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1656-0KK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1656-0KK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}