{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1656-0KK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1656-0KK10","canonicalUrl":"https://aoctrl.com/siemens/5SU1656-0KK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1656-0KK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1656-0KK10 RCBO, 2-pole 1P+N, B-curve 10 A, 30 mA residual current type AC, 6 kA per EN 60898, 15 kA per IEC 60947-2, 2 MW, IP20.","salesMarkdown":"It protects a single-phase final subcircuit against both overload/short-circuit and earth leakage in one unit, saving a DIN-rail position over separate MCB+RCCB. Rated 230/240 V AC at 50 Hz, it carries a B-curve tripping characteristic (instantaneous trip between 3 and 5 times rated current) and a 30 mA residual-current sensitivity of type AC — meaning it detects sinusoidal AC fault currents only, not pulsating DC or smooth DC. That makes it a fit for general-purpose socket-outlet circuits, lighting, and small appliance loads where no variable-speed drives or electronic loads are downstream. ## Temperature derating — the real-world current rating The 10 A nominal rating only holds at 30 °C ambient inside the enclosure. At 40 °C it's 9.5 A; at 50 °C it's 9 A; at 60 °C it's 8.5 A; at 70 °C it's 8 A. The full derating curve is published for every 5 °C step from 30 °C to 70 °C. At 36 mm wide (2 modular units), it occupies two standard 18 mm positions. Depth is 77 mm, installation depth 70 mm — check your enclosure's internal clearance if you're retrofitting into a shallow gland-plate area. Supply can enter from top or bottom; the neutral is switched (1P+N, not 2P). IP20 protection applies only when the distribution board is installed with connected conductors — the busbar stabs and terminals are live when the front cover is off, so standard finger-safe terminal shrouds or a dead-front enclosure are expected. ## Compliance and approvals","metaTitle":"Siemens 5SU1656-0KK10 SENTRON RCBO, B-Curve 10A 30mA, 6kA","metaDescription":"Siemens 5SU1656-0KK10 SENTRON RCBO, 2-pole 1P+N, B-curve 10A, 30mA residual current type AC. 6kA breaking capacity per EN 60898, 15kA per IEC 60947-2. Current production. Quoted to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c4eb5b750b31e27907029be569e93220.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=229795&mlfb=5SU1656-0KK10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1656-0KK10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1656-0KK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1656-0KK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}