{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU1656-0KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU1656-0KK16","canonicalUrl":"https://aoctrl.com/siemens/5SU1656-0KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SU1656-0KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU1656-0KK16 RCBO, 2-pole (1P+N), 16 A rated at 30 °C, B tripping characteristic, AC residual current type, 6 kA per EN 60898, 15 kA per IEC 60947-2.","salesMarkdown":"The Siemens 5SU1656-0KK16 is a 2-pole (1P+N) SENTRON RCBO — a combined miniature circuit breaker and residual current device in a single 36 mm wide (2 MW) module. It protects a 230/240 V AC circuit at 50 Hz, rated 16 A at 30 °C with a B tripping characteristic, and detects AC residual currents. That 15 kA rating gives you headroom in a sub-distribution board fed by a larger transformer — a common spec for packaging lines and conveyor systems. Feed can come from top or bottom — no orientation restriction. Installation depth is 70 mm into the distribution board. ## Thermal derating — what the numbers mean In a warm panel — say 50 °C — the continuous current drops to 14.4 A. At 70 °C it's 12.32 A. If you're packing this RCBO next to other heat sources in a sealed enclosure, use the 50 °C or 60 °C column for your load calculation, not the 30 °C headline number. Construction is halogen-free and silicon-free — relevant if the panel goes into a clean-room or semiconductor-adjacent environment where outgassing matters.","metaTitle":"Siemens 5SU1656-0KK16 SENTRON RCBO, 2-pole 16A B-curve 30mA","metaDescription":"Siemens 5SU1656-0KK16 SENTRON RCBO, 2-pole 1P+N, 16A rated at 30°C, B-curve, AC residual current type. 6kA per EN 60898, 15kA per IEC 60947-2. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/73fc2b1894deb4e566a2f4cfadcc78fe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=101958&mlfb=5SU1656-0KK16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU1656-0KK16/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU1656-0KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU1656-0KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}