{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU9106-1KK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU9106-1KK10","canonicalUrl":"https://aoctrl.com/siemens/5SU9106-1KK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU9106-1KK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU9106-1KK10, RCBO, 1P+N, rated current 10 A, tripping characteristic C, rated residual current 10 mA, breaking capacity 6 kA according to EN 60898, 2 modules wide.","salesMarkdown":"Lifecycle status is current. The residual current element is type AC, rated 10 mA — sensitive enough for personal protection in wet locations but not so low it trips on normal leakage from filters or long cable runs. This is a 1P+N device — it switches the line conductor and provides residual current detection on both line and neutral, but does not switch the neutral. Supply can enter from top or bottom, which simplifies busbar routing in a crowded enclosure. Touch protection is built in. At 40 °C it derates to 9.4 A, at 45 °C to 9.1 A, at 50 °C to 8.7 A, and at 55 °C to 8.1 A (–). If the panel runs warm — adjacent to a transformer or in a non-ventilated enclosure — size up one frame to stay inside the thermal curve. ## Installation notes Mounting position is any orientation. This is an active, current-production Siemens SENTRON part. For volume or scheduled releases, a blanket PO with scheduled releases is the standard commercial posture.","metaTitle":"Siemens 5SU9106-1KK10 SENTRON RCBO, 10A C-curve 10mA, 6kA","metaDescription":"Siemens 5SU9106-1KK10 SENTRON RCBO, 10A rated, C-curve, 10mA RCD, 6kA breaking capacity. 1P+N, 18mm wide. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SU9106-1KK10","Height":"125 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, 6 kA, 1P+N, Type AC, 10 mA, C-Char, In: 10 A, Un AC: 230 V, pigtail 600 mm, solid N","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"10 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"260 g","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.4 A","at 45 °C / rated value":"9.1 A","at 50 °C / rated value":"8.7 A","at 55 °C / rated value":"8.1 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"125 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"10 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"No","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6944ad0d6cb81dc4fdd987aff690e4fa.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629225&mlfb=5SU9106-1KK10"},"ai":{"faq":[{"question":"What is the depth and width of 5SU9106-1KK10?","answer":"Depth 77 mm, width 18 mm (one modular unit), height 125 mm. Installation depth is 70 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU9106-1KK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU9106-1KK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}