{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU9326-1CR16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU9326-1CR16","canonicalUrl":"https://aoctrl.com/siemens/5SU9326-1CR16","factsUrl":"https://aoctrl.com/api/mcp/products/5SU9326-1CR16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU9326-1CR16, RCBO, 2-pole, 16 A (30 °C), C-curve, 6 kA per EN 60898, 4 MW, IP20.","salesMarkdown":"This is the current-production variant, so it's the one to specify for new builds or as a like-for-like spare on an existing SENTRON panel. At 16 A / 30 °C, it handles a 3–4 kW resistive or motor load on a 230/240 V AC supply. The 4 MW width (72 mm) occupies four 18 mm modular units on a DIN rail — check your gland plate fill if you're swapping in a tighter enclosure. Temperature derating is baked in: 14.6 A at 40 °C, 13.9 A at 45 °C, 13.3 A at 50 °C, 12.5 A at 55 °C. The RCBO itself is rated for any mounting position and can be fed from top or bottom, which simplifies wiring in a crowded enclosure. The 5SU9326-1CR16 is listed as current-production (lifecycle stage: current). No last-time-buy or phase-out notice is on record for this order code. The RCBO is halogen-free and silicon-free, rated IP20 with conductors connected and the distribution board installed. The surge voltage resistance is rated at 4 kV, and it withstands a 1 kA surge current (8/20 µs waveform). Compliance documentation (RoHS, REACH) is provided with the brand's standard declaration pack.","metaTitle":"Siemens 5SU9326-1CR16 SENTRON RCBO, 2P 16A C-curve 6kA","metaDescription":"Siemens 5SU9326-1CR16 SENTRON RCBO, 2-pole, 16A rated at 30°C, C-curve, 6kA breaking capacity per EN 60898. Current-production part, sourced to order. Request quote for pricing and","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"72 mm","title":"5SU9326-1CR16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, 6 kA, 2P, Type AC, 30 mA, C-Char, In: 16 A, Un AC: 400 V","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"2P","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"420 g","at 30 °C rated value":"16 A","at 40 °C rated value":"14.6 A","at 45 °C rated value":"13.9 A","at 50 °C rated value":"13.3 A","at 55 °C rated value":"12.5 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"125 V","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"2","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"440 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"6 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"0.75 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c199c53069491f9991f1a0af91da6a06.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629286&mlfb=5SU9326-1CR16"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for 5SU9326-1CR16?","answer":"The part is halogen-free and silicon-free. Standard brand compliance documentation (RoHS, REACH) is provided with the shipment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU9326-1CR16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU9326-1CR16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}