{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU9336-1CN10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU9336-1CN10","canonicalUrl":"https://aoctrl.com/siemens/5SU9336-1CN10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU9336-1CN10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SU9336-1CN10, 3-pole, 10 A, Type C, 6 kA, 400 V AC, 6 MW, halogen-free.","salesMarkdown":"## RCBO for panel builders — what the ratings mean The Siemens 5SU9336-1CN10 is a SENTRON RCD-operated circuit breaker (RCBO) combining overcurrent protection and residual current detection in a single 6-module-wide (108 mm) DIN-rail device. Temperature derating is baked into the spec: at 40 °C the continuous rating drops to 8.9 A, at 50 °C to 8.1 A, and at 55 °C to 7.7 A. If the RCBO sits in a crowded enclosure near transformers or contactors, size the circuit at the ambient-trimmed figure, not the 30 °C headline. The 77 mm depth fits most shallow enclosures; installation depth is 70 mm. Six modular width units (108 mm wide) for three protected poles. That's a tight fit for a 3P RCBO — verify DIN-rail real estate before committing the BOM if the panel is already dense. ## Construction and compliance Surge voltage resistance rated at 4 000 V, surge current resistance 1 kA at 8/20 μs. Insulation voltage 440 V. Operating frequency 50/60 Hz.","metaTitle":"Siemens 5SU9336-1CN10 SENTRON RCBO, 10A Type C, 6kA, 3P","metaDescription":"Siemens SENTRON 5SU9336-1CN10 RCD-operated circuit breaker. 10A Type C, 6kA breaking capacity, 3-pole, 400V AC. Halogen-free. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"108 mm","title":"5SU9336-1CN10","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 6 kA, 3P, Type AC, 30 mA, C-Char, In: 10 A, Un AC: 230 V","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"3P","Number Of Poles":"3","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"400 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"470 g","at 30 °C rated value":"10 A","at 40 °C rated value":"8.9 A","at 45 °C rated value":"8.6 A","at 50 °C rated value":"8.1 A","at 55 °C rated value":"7.7 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"125 V","Number Of Modular Width Units":"6","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"3","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"440 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"6 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"0.75 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c3a1316391d4857856bcf7bb8625f695.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=800735&mlfb=5SU9336-1CN10"},"ai":{"faq":[{"question":"Where can I buy 5SU9336-1CN10 and how is it quoted?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figure is published here."},{"question":"What is the depth of 5SU9336-1CN10?","answer":"77 mm overall depth, with a 70 mm installation depth behind the panel."},{"question":"What is the width of 5SU9336-1CN10?","answer":"108 mm, which corresponds to 6 modular width units on DIN rail."},{"question":"Will 5SU9336-1CN10 drop into a panel specified around 5SU9356-7KK06 without rewiring?","answer":"Both are 3-pole SENTRON RCBOs on the same DIN-rail footprint, but verify the rated current, trip characteristic, and residual current sensitivity of the original spec — the 5SU9336-1CN10 is a 10 A Type C unit, while the 5SU9356-7KK06 may differ. Physical mounting is the same; electrical substitution depends on the circuit's protection requirements."},{"question":"What compliance documentation does Siemens provide for 5SU9336-1CN10?","answer":"The device carries ratings per EN 60898 and IEC 60947-2. Halogen-free and silicon-free construction is declared. Standard Siemens declaration of conformity and product compliance information is available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU9336-1CN10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU9336-1CN10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}