{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU9336-1CN63","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU9336-1CN63","canonicalUrl":"https://aoctrl.com/siemens/5SU9336-1CN63","factsUrl":"https://aoctrl.com/api/mcp/products/5SU9336-1CN63","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU9336-1CN63, 3-pole RCBO, 63 A rated at 30 °C, 30 mA residual current, C-curve, 6 kA breaking capacity, IP20.","salesMarkdown":"The Siemens 5SU9336-1CN63 is a 3-pole RCD-operated circuit breaker (RCBO) from the SENTRON family, combining overcurrent and residual current protection in one 6-module-width unit. The 63 A rating at 30 °C is the headline number for sizing into a distribution board, but the derated values matter for real panel conditions: 58.6 A at 40 °C, 56.1 A at 45 °C, 54.8 A at 50 °C, and 53.6 A at 55 °C. If your enclosure runs warm, the lower figure governs the load you can protect. The 30 mA residual current trip is standard for personnel protection (indirect contact) in TN and TT systems. Occupies 6 modular width units (108 mm) on a DIN rail. Depth is 77 mm, height 90 mm. Installation depth is 70 mm. Mounting position is unrestricted, so it can go sideways or inverted if the cabinet layout demands it. The 5SU9336-1CN63 carries the Siemens SENTRON brand and complies with designation F (protective device). Breaking capacity: 6 kA. Energy limitation class 3 means it lets through limited fault energy, helping with downstream coordination. Rated insulation voltage (Ui) is 440 V. Operating frequency is 50/60 Hz. Test circuit minimum voltage is 125 V.","metaTitle":"Siemens 5SU9336-1CN63 SENTRON RCBO, 63 A, 30 mA, C-curve","metaDescription":"Siemens 5SU9336-1CN63 SENTRON RCD-operated circuit breaker, 3-pole, 63 A at 30 °C, 30 mA residual current, C-curve, 6 kA. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"108 mm","title":"5SU9336-1CN63","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO, Icn: 6 kA, 3P, Type AC, 30 mA, C-Char, In: 63 A, Un AC: 230 V","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"3","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"63 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"470 g","at 30 °C / rated value":"63 A","at 40 °C / rated value":"58.6 A","at 45 °C / rated value":"56.1 A","at 50 °C / rated value":"54.8 A","at 55 °C / rated value":"53.6 A","Number Of Modular Width Units":"6","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"125 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"3","acc. to IEC 60947-2 / rated value":"6 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"440 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8d7951f0363f8bf1efb007a11fa7b681.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=800742&mlfb=5SU9336-1CN63"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU9336-1CN63","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU9336-1CN63 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}