{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU9354-8KK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU9354-8KK06","canonicalUrl":"https://aoctrl.com/siemens/5SU9354-8KK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU9354-8KK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU9354-8KK06, RCBO, 2-pole, 6 A rated, D characteristic, 30 mA residual current, Type A, 10 kA breaking capacity, 2 MWU, IP20.","salesMarkdown":"## Derating and mounting Rated 6 A at 30 °C, but the continuous current drops to 5.64 A at 40 °C and 4.86 A at 55 °C — factor that into your load calculation if the panel runs warm. Mounts in any position, supply from top or bottom, and the 77 mm depth plus 70 mm installation depth fits standard DIN-rail enclosures. IP20 with conductors connected, so it's enclosed-panel only; not for wet or outdoor locations.","metaTitle":"Siemens 5SU9354-8KK06 SENTRON RCBO, 6A D-curve, 30mA, 2-pole","metaDescription":"Siemens 5SU9354-8KK06 SENTRON RCBO, 6 A rated, D tripping characteristic, 30 mA residual current, Type A, 10 kA breaking capacity, 2-pole, 2 MWU. Current production. Quoted to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","acc. to IEC 81346-2":"F","at AC / rated value":"6 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"285 g","at 30 °C / rated value":"6 A","at 40 °C / rated value":"5.64 A","at 45 °C / rated value":"5.46 A","at 50 °C / rated value":"5.22 A","at 55 °C / rated value":"4.86 A","Number Of Modular Width Units":"2","Tripping Characteristic Class":"D","acc. to EN 60898 / rated value":"10 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"10 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/79f6610cfebb3bc98ed563eb1e55c601.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629329&mlfb=5SU9354-8KK06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU9354-8KK06/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SU9354-8KK06?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time; the part is sourced through independent distribution channels."},{"question":"What is 5SU9354-8KK06's listed depth?","answer":"The depth is 77 mm, with an installation depth of 70 mm."},{"question":"What is 5SU9354-8KK06's listed width?","answer":"The width is 36 mm, which corresponds to 2 modular width units (MWU)."},{"question":"What compliance documentation does this brand provide for 5SU9354-8KK06?","answer":"The part is certified to EN 60898 and IEC 60947-2 for breaking capacity, and carries the SENTRON brand from Siemens. Halogen-free and silicon-free construction. Specific RoHS/REACH/UL declarations are available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU9354-8KK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU9354-8KK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}