{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU9356-1KN10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU9356-1KN10","canonicalUrl":"https://aoctrl.com/siemens/5SU9356-1KN10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU9356-1KN10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU9356-1KN10, RCBO, 1P+N, 10 A, C-curve, 6 kA (EN 60898) / 10 kA (IEC 60947-2), 2 MW, 77×36×90 mm.","salesMarkdown":"It protects a single-phase final subcircuit against overload, short-circuit, and earth leakage. The 1P+N design switches the line conductor only; the neutral is switched internally for isolation but not protected. Depth is 77 mm, installation depth 70 mm — verify enclosure depth clearance, especially in shallow gland-plate areas. Supply can enter from top or bottom; no mandatory orientation. IP20 with the distribution board installed and conductors connected — not rated for wet or dusty environments. Ambient temperature range is -40 °C to 75 °C, with a derating curve above 30 °C: 9.4 A at 40 °C, 9.1 A at 45 °C, 8.7 A at 50 °C, 8.1 A at 55 °C. In a hot enclosure, size the load accordingly.","metaTitle":"Siemens 5SU9356-1KN10 SENTRON RCBO, 10 A C-curve, 6/10 kA","metaDescription":"Siemens 5SU9356-1KN10 SENTRON RCBO, 1P+N, 10 A rated, C-curve, 6 kA (EN 60898) / 10 kA (IEC 60947-2). Active production. 2 MW wide. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"280 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.4 A","at 45 °C rated value":"9.1 A","at 50 °C rated value":"8.7 A","at 55 °C rated value":"8.1 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"10 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"0.75 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/79f6610cfebb3bc98ed563eb1e55c601.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629366&mlfb=5SU9356-1KN10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU9356-1KN10/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 5SU9356-1KN10 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the depth and width of the 5SU9356-1KN10?","answer":"Depth is 77 mm, width is 36 mm (2 modular units), height is 90 mm. Installation depth is 70 mm."},{"question":"What compliance documentation does Siemens provide for the 5SU9356-1KN10?","answer":"The part is halogen-free and silicon-free. It carries ratings per EN 60898 and IEC 60947-2. Specific RoHS/REACH/UL declarations should be requested with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU9356-1KN10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU9356-1KN10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}