{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU9356-7KN10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU9356-7KN10","canonicalUrl":"https://aoctrl.com/siemens/5SU9356-7KN10","factsUrl":"https://aoctrl.com/api/mcp/products/5SU9356-7KN10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU9356-7KN10, 2-pole RCBO, 10 A rated, Type A residual current, 30 mA trip, C tripping characteristic, 6 kA breaking capacity per EN 60898.","salesMarkdown":"The 10 A rating applies at 30 °C ambient. At 40 °C the continuous current must be derated to 9.4 A, at 45 °C to 9.1 A, at 50 °C to 8.7 A, and at 55 °C to 8.1 A. This matters when the RCBO is installed in a crowded enclosure with multiple heat sources — the derating curve is the binding limit, not the 10 A label. Installation depth is 70 mm, and the overall depth including the front is 77 mm. The supply cord can enter from either top or bottom, which simplifies wiring in tight enclosures. Touch protection is provided on the terminals. The IP20 rating applies only when the distribution board is installed with connected conductors — not a standalone ingress protection for wet environments. The part is halogen-free and silicon-free, which may be relevant for certain environmental compliance requirements. It carries the SENTRON brand from Siemens and is classified per EN 61346-2 and IEC 81346-2 as function F.","metaTitle":"Siemens 5SU9356-7KN10 SENTRON RCBO, 2-pole, 10 A, Type A, 30","metaDescription":"Siemens 5SU9356-7KN10 SENTRON RCBO, 2-pole, 10 A, Type A, 30 mA, C-curve, 6 kA breaking capacity. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"36 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","at AC / rated value":"10 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Energy Limitation Class":"3","Weight / With Packaging":"280 g","according to EN 61346-2":"F","at 30 °C / rated value":"10 A","at 40 °C / rated value":"9.4 A","at 45 °C / rated value":"9.1 A","at 50 °C / rated value":"8.7 A","at 55 °C / rated value":"8.1 A","according to IEC 81346-2":"F","Number Of Modular Width Units":"2","Tripping Characteristic Class":"C","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","Product Feature / Touch Protection":"Yes","according to EN 60898 / rated value":"6 kA","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"264 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","according to IEC 60947-2 / rated value":"10 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/79f6610cfebb3bc98ed563eb1e55c601.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629392&mlfb=5SU9356-7KN10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU9356-7KN10/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SU9356-7KN10?","answer":"The rated breaking capacity is 6 kA according to EN 60898. This is the maximum prospective fault current the device can safely interrupt under standard test conditions."},{"question":"Where can I buy 5SU9356-7KN10 and how is it quoted?","answer":"This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at the time of quotation — no stock or price figures are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU9356-7KN10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU9356-7KN10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}