{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SU9604-1KK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SU9604-1KK06","canonicalUrl":"https://aoctrl.com/siemens/5SU9604-1KK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SU9604-1KK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SU9604-1KK06, RCBO, 1P+N, 6 A, C-curve, 10 kA, Type A, 30 mA, 1 MW.","salesMarkdown":"The Siemens 5SU9604-1KK06 is a SENTRON RCBO — a combined RCD and MCB in a single 1-module-wide (18 mm) package. The 1P+N design switches the line pole and monitors the neutral; the neutral is not switched. The 10 kA breaking capacity (EN 60898 and IEC 60947-2) means this RCBO can safely interrupt a fault current up to 10,000 A — sufficient for most domestic and light commercial installations where the prospective short-circuit current at the board is under that threshold. The Type A residual current detection catches pulsating DC fault currents (e.g., from rectifiers or switched-mode supplies) that a Type AC device would miss. The 30 mA sensitivity provides personal protection against direct contact. Temperature derating is built in: at 40 °C the continuous rating drops to 5.64 A, at 50 °C to 5.22 A. If the board runs warm, size the circuit load accordingly. The device is rated for overvoltage category III (distribution level) and pollution degree 2, which covers typical indoor panel environments. At 18 mm (1 MW) wide, it occupies a single module slot — critical when retrofitting into a crowded board. IP20 protection applies once the distribution board is installed and conductors are connected.","metaTitle":"Siemens 5SU9604-1KK06 SENTRON RCBO, 6 A, 10 kA, Type A, 30 m","metaDescription":"Siemens 5SU9604-1KK06 SENTRON RCBO, 6 A rated, 10 kA breaking capacity (EN 60898), Type A, 30 mA residual current, 1 MW wide. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"125 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230/240 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCD-operated circuit breaker","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"260 g","at 30 °C rated value":"6 A","at 40 °C rated value":"5.64 A","at 45 °C rated value":"5.46 A","at 50 °C rated value":"5.22 A","at 55 °C rated value":"4.86 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"125 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"10 kA","insulation voltage (Ui) rated value":"264 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"10 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"0.75 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/28c2cb3e4e24560a0153c76b134ac810.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=629432&mlfb=5SU9604-1KK06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SU9604-1KK06/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SU9604-1KK06?","answer":"10 kA per both EN 60898 and IEC 60947-2, which covers most residential and light commercial distribution boards."},{"question":"What is the difference between this RCBO and a standard MCB?","answer":"This unit combines overcurrent protection (MCB function) with residual current protection (RCD function) in one module. A standard MCB only protects against overload and short circuit; the 5SU9604-1KK06 also detects earth leakage at 30 mA (Type A), providing personal shock protection."},{"question":"Where can I buy 5SU9604-1KK06 and how is it quoted?","answer":"It is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — no stock or price figures are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SU9604-1KK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SU9604-1KK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}