{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1313-1GV10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1313-1GV10","canonicalUrl":"https://aoctrl.com/siemens/5SV1313-1GV10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1313-1GV10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 10 A rated, C-curve, 30 mA residual current, 4.5 kA breaking capacity, 1P+N, 18 mm width.","salesMarkdown":"It integrates a C-curve miniature circuit breaker (MCB) characteristic with a 30 mA residual-current device (RCD) in one housing, saving a DIN-rail position compared to separate devices. The 30 mA residual-current element provides personal protection against direct contact — the standard threshold for socket-outlet circuits in most IEC-based installations. ## Temperature derating — the real-world current limit The 10 A rating holds only up to 30 °C ambient. Above that, the continuous current must be derated: 9.4 A at 40 °C, 8.8 A at 45 °C, 8.1 A at 60 °C, and 7.4 A at 70 °C (–). In a crowded distribution board where internal temperature rises, the effective ampacity can be significantly lower than the label — plan the load accordingly. Snap-on mounting to DIN rail, any position. Supply can enter from top or bottom. IP20 rating applies only when installed in a distribution board with conductors connected — the device itself is not touch-proof without the enclosure.","metaTitle":"Siemens SENTRON 5SV1313-1GV10 RCBO, 10A C-curve 30mA, 1P+N","metaDescription":"Siemens SENTRON 5SV1313-1GV10 RCBO, 10A rated, C-curve, 30mA residual current, 4.5kA breaking capacity, 1P+N, 18mm wide. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1313-1GV10","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"5SV1 RCBO TypeAC 30mA C10 4.5kA 1+N 1MW, Big Pack 12 pcs","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"10 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Weight With Packaging":"133 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.4 A","at 45 °C rated value":"9.1 A","at 50 °C rated value":"8.8 A","at 55 °C rated value":"8.4 A","at 60 °C rated value":"8.1 A","at 65 °C rated value":"7.7 A","at 70 °C rated value":"7.4 A","Energy Limitation Class":"3","according to EN 61346-2":"F","according to IEC 81346-2":"F","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"4.5 kA","Tripping Fault Current Rated Value":"30 mA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"5 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Switching Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"0.95 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1265703&mlfb=5SV1313-1GV10"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV1313-1GV10?","answer":"4.5 kA per EN 60898. That standard covers household and similar fixed installations."},{"question":"What compliance documentation is available for 5SV1313-1GV10?","answer":"The device is halogen-free and silicon-free. It carries the SENTRON brand and is designed per EN 60898 and IEC 61346-2 / 81346-2. Full RoHS/REACH/UL declarations are typically available from the manufacturer upon request."},{"question":"Where can I buy 5SV1313-1GV10 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1313-1GV10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1313-1GV10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}