{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1313-1KK04","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1313-1KK04","canonicalUrl":"https://aoctrl.com/siemens/5SV1313-1KK04","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1313-1KK04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 1P+N, Type C, 4 A, 4.5 kA per EN 60898, 5 kA per IEC 60947-2, 50 Hz, 230 V AC, 18 mm width, IP20.","salesMarkdown":"It combines a Type C thermal-magnetic trip curve with ground-fault detection in a single 18 mm modular-width unit — one pole protected, the neutral switched but not protected. Rated 4 A at 30 °C and 230 V AC, 50 Hz, it's sized for lighting circuits, small motor loads, or control transformers where you need both short-circuit and earth-leakage protection in one DIN-rail slot. The RCBO itself is instantaneous-trip (no time delay on the residual side), meaning it clears ground faults in under 40 ms, which keeps the shock risk low and meets the disconnection times in IEC 60364. Breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — enough for most final sub-circuits in a 230/400 V distribution board. ## Deployment and panel integration The IP20 rating holds only when the distribution board is installed and conductors are connected; treat it as a panel-internal device, not for wet-area standalone use. Temperature derating is published across the range: 4 A at 30 °C, 3.8 A at 40 °C, 3.6 A at 50 °C, 3.4 A at 60 °C, and 3.2 A at 70 °C. If this RCBO sits in a sealed, sun-loaded cabinet, the 40 °C or 50 °C column is the one that governs the load you can actually protect.","metaTitle":"Siemens SENTRON 5SV1313-1KK04 RCBO, Type C, 4A, 4.5kA","metaDescription":"Siemens SENTRON 5SV1313-1KK04 RCBO, 1P+N, Type C, 4A, 4.5kA per EN 60898. Current production. Available to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1313-1KK04","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 4.5 kA type AC 30 mA C4","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"4 A","at 40 °C rated value":"3.8 A","at 45 °C rated value":"3.72 A","at 50 °C rated value":"3.6 A","at 55 °C rated value":"3.52 A","at 60 °C rated value":"3.4 A","at 65 °C rated value":"3.32 A","at 70 °C rated value":"3.2 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"4.5 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"5 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027003&mlfb=5SV1313-1KK04"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV1313-1KK04?","answer":"4.5 kA per EN 60898 and 5 kA per IEC 60947-2. The higher IEC figure gives you some headroom if the fault level at the panel is near the EN limit."},{"question":"Where can I buy 5SV1313-1KK04 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock numbers or prices are listed here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1313-1KK04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1313-1KK04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}