{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1313-1KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1313-1KK16","canonicalUrl":"https://aoctrl.com/siemens/5SV1313-1KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1313-1KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SV1313-1KK16, 1P+N, 16 A at 30 °C, C characteristic, 4.5 kA (EN 60898) / 5 kA (IEC 60947-2), 1 MWU, IP20.","salesMarkdown":"It protects a single-phase final circuit against overload, short-circuit, and earth leakage. The 1P+N design means the line pole is switched and protected; the neutral pole is switched but not protected. The 4.5 kA breaking capacity per EN 60898 covers most domestic and light commercial installations; the 5 kA rating per IEC 60947-2 gives a bit more headroom for industrial panels where the prospective fault current is higher. The C curve (5–10× In) means it will hold through the start-up surge of a small compressor or pump without nuisance tripping, but still clears a bolted fault fast enough to limit let-through energy to Energy Limitation Class 3. ## Temperature derating — the real-world current rating The 16 A rating holds only up to 30 °C ambient inside the distribution board. Above that, the thermal-magnetic trip element must be derated: 15.2 A at 40 °C, 14.72 A at 45 °C, 14.24 A at 50 °C, 13.76 A at 55 °C, 13.28 A at 60 °C, 12.8 A at 65 °C, and 12.32 A at 70 °C. Plan the load accordingly, or the bimetal strip will trip on a sustained current well below 16 A. At 18 mm wide (1 MWU), it occupies one slot in a distribution board. Depth is 77 mm, installation depth 70 mm — check your enclosure depth if using a shallow flush-mount box. IP20 rating applies only when the distribution board is installed and conductors are connected; the front face is finger-safe, but the terminals are not touch-proof with the cover open. Any mounting position is permitted, so it can be installed sideways or inverted if the enclosure layout demands it.","metaTitle":"Siemens 5SV1313-1KK16 SENTRON RCBO, 16A C-curve, 1P+N, 4.5kA","metaDescription":"Siemens 5SV1313-1KK16 SENTRON RCBO, 16 A rated at 30 °C, C tripping characteristic, 1P+N, 4.5 kA per EN 60898, 5 kA per IEC 60947-2. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1313-1KK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 4.5 kA type AC 30 mA C16","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"16 A","at 40 °C rated value":"15.2 A","at 45 °C rated value":"14.72 A","at 50 °C rated value":"14.24 A","at 55 °C rated value":"13.76 A","at 60 °C rated value":"13.28 A","at 65 °C rated value":"12.8 A","at 70 °C rated value":"12.32 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"4.5 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"5 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027007&mlfb=5SV1313-1KK16"},"ai":{"faq":[{"question":"Where can I buy the 5SV1313-1KK16?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of the 5SV1313-1KK16?","answer":"Rated 4.5 kA per EN 60898 and 5 kA per IEC 60947-2. The higher IEC rating gives some margin for industrial panels with higher prospective fault current."},{"question":"What does the C tripping characteristic mean for this RCBO?","answer":"The C curve trips at 5 to 10 times the rated current (80–160 A for this 16 A unit). It is designed for circuits with moderate inrush — small motors, transformers, lighting — and avoids nuisance trips from brief start-up surges."},{"question":"What compliance documentation is available for the 5SV1313-1KK16?","answer":"The part is halogen-free and silicon-free. It carries ratings per EN 60898 and IEC 60947-2, and is designed for overvoltage category III, pollution degree 2. Specific RoHS/REACH/UL declarations should be requested at quote time from the supplier."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1313-1KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1313-1KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}