{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1313-6KK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1313-6KK10","canonicalUrl":"https://aoctrl.com/siemens/5SV1313-6KK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1313-6KK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1313-6KK10 RCBO, 1P+N, B-curve 10 A, 30 mA Type A, 4.5 kA breaking capacity, 18 mm width, IP20.","salesMarkdown":"It's rated 10 A with a B-curve overcurrent characteristic and 30 mA Type A residual current protection, breaking capacity 4.5 kA per EN 60898. This is the part you spec into a final subcircuit where both overcurrent and earth-fault protection are needed in one DIN-rail slot, saving a module width versus separate MCB + RCCD. The B-curve means the magnetic trip operates at 3 to 5 times rated current — so 30 to 50 A for this 10 A unit. The 30 mA residual trip covers basic additional protection against direct contact; Type A detects pulsating DC fault currents, which matters for circuits with single-phase rectifiers, electronic loads, or variable-speed drives downstream. In a domestic or light commercial distribution board with a typical upstream transformer impedance, 4.5 kA is adequate for most final circuits. If your fault level exceeds that, you need a higher-rated upstream device or a current-limiting MCB upstream to coordinate. The 1P+N design switches the line pole only; the neutral is switched but not protected. That's standard for single-phase final circuits where the neutral is not overload-protected. The module occupies one 18 mm modular unit, so it fits any DIN-rail enclosure with standard 18 mm pitch. Thermal derating is published: 10 A at 30 °C ambient, dropping to 9.4 A at 40 °C, 8.8 A at 45 °C, and 7.4 A at 70 °C (–). If your distribution board runs hot — say above 40 °C in a sealed enclosure — size the circuit load to the derated figure, not the 30 °C nameplate. This RCBO belongs in the final distribution board of a commercial or light industrial installation — protecting a single-phase socket circuit, lighting subcircuit, or small equipment feed. The SENTRON series is Siemens' standard for panelboard protection; the 18 mm width and 1P+N format make it a direct fit for any DIN-rail enclosure. IP20 rating means it's for dry indoor use inside a distribution board with connected conductors — not for wet or outdoor locations without an outer enclosure.","metaTitle":"Siemens 5SV1313-6KK10 SENTRON RCBO, 10A B-Curve, 30mA, 1P+N","metaDescription":"Siemens 5SV1313-6KK10 SENTRON RCBO, 10A rated, B-curve, 30mA Type A residual current, 4.5kA breaking capacity, 1P+N, 18mm wide. Current lifecycle. Available to order, quoted on req","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"18 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027009&mlfb=5SV1313-6KK10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV1313-6KK10/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1313-6KK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1313-6KK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}