{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1313-6KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1313-6KK16","canonicalUrl":"https://aoctrl.com/siemens/5SV1313-6KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1313-6KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1313-6KK16, RCBO, 1P+N, B-curve, 16 A at 30 °C, 4.5 kA (EN 60898), 1 MW wide, depth 77 mm.","salesMarkdown":"Rated 16 A at 30 °C, the part carries a full thermal derating table through 70 °C — at 40 °C it's 15.2 A, at 50 °C 14.4 A, at 60 °C 13.6 A, and at 70 °C 12.8 A (–). That matters for a crowded enclosure: if the panel ambient runs 50 °C, the continuous load limit drops to 14.4 A, not the nameplate 16 A. Breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2 — sufficient for most commercial and light industrial sub-distribution where the upstream transformer limits fault current below those levels. The housing is 1 MW wide (18 mm per), depth 77 mm, installation depth 70 mm. Mounting position any, supply feed either top or bottom. IP20 with the distribution board installed and conductors connected — it's a panel-interior device, not a field-mounted enclosure. Degree of pollution 2, overvoltage category III. Energy limitation class 3. Surge voltage resistance 4 000 V. Insulation voltage (Ui) rated 253 V.","metaTitle":"Siemens 5SV1313-6KK16 SENTRON RCBO, B16, 1P+N, 4.5 kA","metaDescription":"Siemens 5SV1313-6KK16 SENTRON RCBO, 16 A B-curve, 1P+N, 4.5 kA per EN 60898. Thermal derating from 30–70 °C. 1 MW wide, depth 77 mm. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1313-6KK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 4.5 kA type A 30 mA B16","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"16 A","at 40 °C rated value":"15.2 A","at 45 °C rated value":"14.88 A","at 50 °C rated value":"14.4 A","at 55 °C rated value":"14.08 A","at 60 °C rated value":"13.6 A","at 65 °C rated value":"13.28 A","at 70 °C rated value":"12.8 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"1","according to EN 60898 rated value":"4.5 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"5 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027011&mlfb=5SV1313-6KK16"},"ai":{"faq":[{"question":"Will 5SV1313-6KK16 drop into a panel specified around 5SL6006-7?","answer":"The 5SL6006-7 is a Siemens MCB (no RCD), not an RCBO. The 5SV1313-6KK16 adds residual current protection in the same 1 MW footprint and similar depth, but the wiring differs — the neutral must pass through the RCBO. Mechanical fit on the DIN rail is the same, but the circuit design and terminal connections are not drop-in without rewiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1313-6KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1313-6KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}