{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1313-7KK04","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1313-7KK04","canonicalUrl":"https://aoctrl.com/siemens/5SV1313-7KK04","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1313-7KK04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 1P+N, 4 A at 30 °C, C tripping characteristic, breaking capacity 4.5 kA (EN 60898) / 5 kA (IEC 60947-2), 1 MW width, IP20, current production.","salesMarkdown":"The breaking capacity is 4.5 kA per EN 60898 and 5 kA per IEC 60947-2, which covers most standard final subcircuits in residential and light commercial distribution boards. The 1P+N design (one protected pole plus a switched neutral) fits single-phase final circuits where the neutral is switched but not protected against overcurrent. Rated insulation voltage (Ui) is 253 V, and surge voltage resistance is 4 000 V. The overvoltage category is III, and the degree of pollution is 2 — both standard for fixed-installation distribution boards. The operating frequency is 50 Hz. The energy limitation class is 3, meaning the let-through energy is limited to reduce stress on downstream equipment during a fault. The minimum test voltage is 195 V.","metaTitle":"Siemens SENTRON 5SV1313-7KK04 RCBO, 1P+N, 4A, C-curve, 4.5kA","metaDescription":"Siemens SENTRON 5SV1313-7KK04 RCBO, 1P+N, 4A rated at 30°C, C tripping characteristic, breaking capacity 4.5 kA (EN 60898) / 5 kA (IEC 60947-2). Current production. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1313-7KK04","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 4.5 kA type A 30 mA C4","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"4 A","at 40 °C rated value":"3.8 A","at 45 °C rated value":"3.72 A","at 50 °C rated value":"3.6 A","at 55 °C rated value":"3.52 A","at 60 °C rated value":"3.4 A","at 65 °C rated value":"3.32 A","at 70 °C rated value":"3.2 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"4.5 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"5 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027013&mlfb=5SV1313-7KK04"},"ai":{"faq":[{"question":"Where can I buy 5SV1313-7KK04 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 5SV1313-7KK04's listed depth?","answer":"The overall depth is 77 mm, with an installation depth of 70 mm."},{"question":"What is 5SV1313-7KK04's listed width?","answer":"The width is 18 mm, which is one modular width unit for DIN-rail mounting."},{"question":"Will 5SV1313-7KK04 drop into a panel specified around 5SV9316-1NK06 without rewiring?","answer":"Both are 1 MW wide (18 mm) DIN-rail RCBOs, so the physical footprint and wiring positions are identical. However, verify the rated current and tripping characteristic of the panel design — the 5SV1313-7KK04 is a 4 A C-curve unit, while the peer part may differ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1313-7KK04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1313-7KK04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}