{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-0KK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-0KK10","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-0KK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-0KK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SV1316-0KK10, 1P+N, 10 A rated at 30 °C, B-curve, 6 kA (EN 60898) / 25 kA (IEC 60947-2), 50 Hz, 18 mm wide, IP20.","salesMarkdown":"The Siemens SENTRON 5SV1316-0KK10 is a 1P+N RCBO (residual current operated circuit breaker with integral overcurrent protection) rated 10 A at 30 °C with a B tripping characteristic, designed for 50 Hz systems. The part is instantaneous-trip design (no intentional delay), so it clears fast on hard faults. ## Derating and ambient limits Above that, derate linearly: 9.4 A at 40 °C, 9.1 A at 45 °C, 8.8 A at 50 °C, 8.4 A at 55 °C, 8.1 A at 60 °C, 7.7 A at 65 °C, and 7.4 A at 70 °C. IP20 rating applies only when the distribution board is installed with conductors connected — it's not a standalone IP20 device for open-panel use.","metaTitle":"Siemens SENTRON 5SV1316-0KK10 RCBO, 10 A, B-curve, 1P+N, 6 k","metaDescription":"Siemens SENTRON 5SV1316-0KK10 RCBO, 10 A rated, B tripping characteristic, 1P+N, 6 kA per EN 60898, 25 kA per IEC 60947-2. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1316-0KK10","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 6 kA type AC 30 mA B10","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"10 A","at 40 °C rated value":"9.4 A","at 45 °C rated value":"9.1 A","at 50 °C rated value":"8.8 A","at 55 °C rated value":"8.4 A","at 60 °C rated value":"8.1 A","at 65 °C rated value":"7.7 A","at 70 °C rated value":"7.4 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"25 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027019&mlfb=5SV1316-0KK10"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV1316-0KK10?","answer":"Rated 6 kA according to EN 60898 for standard domestic/commercial circuits, and 25 kA according to IEC 60947-2 for industrial panel duty — the 25 kA figure is the one to use when coordinating with upstream protective devices in a high-fault installation."},{"question":"What is the width of 5SV1316-0KK10?","answer":"18 mm, which is one modular unit (1 MW). It fits a standard DIN-rail slot without crowding adjacent breakers."},{"question":"Where can I buy 5SV1316-0KK10?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quotation."},{"question":"What compliance documentation does Siemens provide for 5SV1316-0KK10?","answer":"The part carries a halogen-free and silicon-free designation, and is designed to EN 60898 and IEC 60947-2. Specific RoHS/REACH declarations and the CE/UKCA marking are available from the manufacturer's documentation portal for this SENTRON order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-0KK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-0KK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}