{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-0KK13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-0KK13","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-0KK13","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-0KK13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1 series RCBO, 13 A rated current, tripping characteristic B, 6 kA breaking capacity per EN 60898, 1P+N, 18 mm width, instantaneous design.","salesMarkdown":"## Thermal derating and power dissipation The 5SV1316-0KK13: The rated current of 13 A applies at 30 °C ambient. The unit derates linearly: 12.35 A at 40 °C, 11.96 A at 45 °C, 11.57 A at 50 °C, 11.18 A at 55 °C, 10.79 A at 60 °C, 10.4 A at 65 °C, and 10.01 A at 70 °C. Maximum power dissipation is 2.6 W. Panel builders should account for this heat load when calculating enclosure thermal rise, especially in densely populated DIN-rail assemblies. ## Dimensions and installation Installation depth behind the panel is 70 mm. Supply connection can be from either top or bottom. Conductor cross-section range is 0.75 to 16 mm² for both solid and stranded wire. The device is halogen-free and silicon-free. Overvoltage category is III. Energy limiting class is 3. The function code per DIN EN 61346-2 and DIN EN 81346-2 is F. The design series is 5SV1. The minimum test voltage for testing equipment is 195 V.","metaTitle":"Siemens 5SV1316-0KK13 SENTRON RCBO, 13A, Type B, 6kA, 1P+N","metaDescription":"Siemens SENTRON 5SV1316-0KK13 RCBO, 13 A rated, tripping characteristic B, 6 kA breaking capacity per EN 60898, 1P+N, 18 mm width. Current-production part, sourced to order. Reques","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Solid":"0.75 ... 16 mm²","Width":"18 mm","title":"5SV1316-0KK13","Height":"90 mm","Maximum":"2.6 W","Stranded":"0.75 ... 16 mm²","at 30 Cel":"13 A","at 40 Cel":"12.35 A","at 45 Cel":"11.96 A","at 50 Cel":"11.57 A","at 55 Cel":"11.18 A","at 60 Cel":"10.79 A","at 65 Cel":"10.4 A","at 70 Cel":"10.01 A","description":"RCBO compact 1P+N 6 kA type AC 30 mA B13","Halogen-Free":"Yes","Silicon-Free":"Yes","During Storage":"-40 ... +75 °C","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-25 ... +45 °C","Product designation":"RCBO","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage category":"III","Design of the product":"Instantaneous","Energy limiting class":"3","Number of width units":"1","Type of fault current":"AC","Number of poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SV1","Current / at AC / rated value":"13 A","Tripping characteristic class":"B","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / of power supply cord":"Either top or bottom","Number of poles / with protection":"1","acc. to IEC 60947-2 / rated value":"15 kA","Product feature / Touch protection":"Yes","Supply voltage frequency / rated value":"50 Hz","Tripping residual current / rated value":"30 mA","Influence of the surrounding temperature":"Max. 95% humidity","Tightening torque / with screw-type terminals":"1.2 ... 2 N·m","Product function / neutral conductor switching":"Yes","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027020&mlfb=5SV1316-0KK13"},"ai":{"faq":[{"question":"Where can I buy 5SV1316-0KK13 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 5SV1316-0KK13's listed depth?","answer":"The listed depth is 77 mm, with an installation depth of 70 mm behind the panel."},{"question":"What conductor cross-section does 5SV1316-0KK13 accept?","answer":"It accepts solid and stranded conductors from 0.75 to 16 mm²."},{"question":"What compliance documentation is available for 5SV1316-0KK13?","answer":"The device is halogen-free and silicon-free. It carries an overvoltage category III rating and is designed per EN 60898 with a 6 kA breaking capacity. The function code per DIN EN 61346-2 and DIN EN 81346-2 is F."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-0KK13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-0KK13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}