{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-0KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-0KK16","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-0KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-0KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1316-0KK16 RCBO, 1P+N, 16 A (30 °C), 30 mA, tripping characteristic B, 6 kA (EN 60898) / 15 kA (IEC 60947-2), 1 MW, IP20.","salesMarkdown":"It combines a 30 mA residual current device (RCD) with a Type B MCB in a single 18 mm wide module — one modular width unit. That means it fits a standard DIN-rail enclosure and takes up the same slot as a single-pole MCB, which matters when panel space is tight and you need both earth-leakage and overcurrent protection on a final subcircuit. Rated 16 A at 30 °C ambient, it derates to 12.8 A at 70 °C — the full thermal curve is listed, so you can size it for the actual cabinet temperature without guessing. The tripping characteristic is B (3-5 In), the standard for general-purpose socket circuits and lighting in residential and commercial panels where inrush is modest. If you're looking at a panel originally built around the 5SY4116-7CV (a Siemens MCB-only, no RCD), the 5SV1316-0KK16 won't drop in without rewiring — the RCBO adds the residual-current module and requires the neutral connection that a plain MCB doesn't. But if the spec calls for combined protection in one module width, this is the direct fit. Mounts in any position on DIN rail. Depth is 77 mm overall, installation depth 70 mm — that 7 mm difference is the front projection of the toggle and test button. IP20 with connected conductors in an installed distribution board, so it's for enclosed panels, not open washdown areas. The 4 kV surge voltage rating (impulse withstand) aligns with overvoltage category III for fixed installations.","metaTitle":"Siemens 5SV1316-0KK16 SENTRON RCBO, 16 A, 30 mA, Type B, 6 k","metaDescription":"Siemens 5SV1316-0KK16 SENTRON RCBO, 1P+N, 16 A rated at 30 °C, 30 mA residual current, tripping characteristic B, 6 kA breaking capacity per EN 60898, 15 kA per IEC 60947-2. Curren","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1316-0KK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 6 kA type AC 30 mA B16","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"16 A","at 40 °C rated value":"15.2 A","at 45 °C rated value":"14.88 A","at 50 °C rated value":"14.4 A","at 55 °C rated value":"14.08 A","at 60 °C rated value":"13.6 A","at 65 °C rated value":"13.28 A","at 70 °C rated value":"12.8 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"15 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027021&mlfb=5SV1316-0KK16"},"ai":{"faq":[{"question":"Will 5SV1316-0KK16 drop into a panel that was specified around 5SY4116-7CV without rewiring?","answer":"No. The 5SV1316-0KK16 is an RCBO requiring a neutral connection for the residual-current module; the 5SY4116-7CV is a single-pole MCB that switches only the phase. The panel would need rewiring to add the neutral path. Physical dimensions are the same (1 MW, 18 mm), but the circuit topology differs."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-0KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-0KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}