{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-1KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-1KK16","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-1KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-1KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1316-1KK16 RCBO, 1P+N, 16 A rated at 30 °C, C-curve, 6 kA per EN 60898, 10 kA per IEC 60947-2, 1-module wide.","salesMarkdown":"## Siemens 5SV1316-1KK16 — SENTRON RCBO, 1P+N, 16 A, C-curve The Siemens 5SV1316-1KK16 is a 1P+N residual current operated circuit breaker (RCBO) from the SENTRON family, combining overcurrent and earth-fault protection in a single 18 mm wide module. The breaking capacity is 6 kA per EN 60898 for domestic/commercial panels and 10 kA per IEC 60947-2 for industrial distribution boards — that 10 kA figure is the one to use when coordinating with an upstream MCCB in an industrial panel. This is a 2-pole device (1P+N) with protection on the live pole only — the neutral is switched but not monitored for overcurrent. It's designed for single-phase final circuits where you need both fault protection and overcurrent protection in one DIN-rail slot. The 16 A rating holds at 30 °C ambient, but it derates linearly as panel temperature climbs: 15.2 A at 40 °C, 14.72 A at 45 °C, 14.24 A at 50 °C, 13.76 A at 55 °C, 13.28 A at 60 °C, 12.8 A at 65 °C, and 12.32 A at 70 °C. If the panel runs hot, size up or leave a spare slot for airflow. Rated insulation voltage is 253 V, surge voltage resistance is 4 kV, and the minimum test voltage is 195 V. Operating frequency is 50 Hz only — there's no 60 Hz rating in the spec, so verify compatibility if the site uses 60 Hz supply. Height is 90 mm. The IP20 rating applies only when the distribution board is installed with connected conductors — it's not a standalone weatherproof device. Spring-cage terminals accept standard copper conductors; no special tools beyond a screwdriver for the clamping screws.","metaTitle":"Siemens 5SV1316-1KK16 SENTRON RCBO, 1P+N, 16 A, C-curve, 6 k","metaDescription":"Siemens 5SV1316-1KK16 SENTRON RCBO, 1P+N, 16 A at 30°C, C-curve, 6 kA per EN 60898, 10 kA per IEC 60947-2. 18 mm wide. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1316-1KK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 6 kA type AC 30 mA C16","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"16 A","at 40 °C rated value":"15.2 A","at 45 °C rated value":"14.72 A","at 50 °C rated value":"14.24 A","at 55 °C rated value":"13.76 A","at 60 °C rated value":"13.28 A","at 65 °C rated value":"12.8 A","at 70 °C rated value":"12.32 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"10 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027027&mlfb=5SV1316-1KK16"},"ai":{"faq":[{"question":"Where can I buy 5SV1316-1KK16 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Contact us with your quantity and target delivery window; availability and current pricing are confirmed at quote time."},{"question":"What is 5SV1316-1KK16's listed depth (77 mm) on this component line?","answer":"The overall depth is 77 mm, with an installation depth of 70 mm behind the DIN-rail mounting surface."},{"question":"What is 5SV1316-1KK16's listed width (18 mm) on this component line?","answer":"Width is 18 mm, which is one modular unit (1 MW) on standard DIN-rail distribution boards."},{"question":"What compliance documentation does this brand provide for 5SV1316-1KK16?","answer":"The part is halogen-free and silicon-free. It carries ratings per EN 60898 (6 kA) and IEC 60947-2 (10 kA), with overvoltage category III and pollution degree 2. Standard Siemens documentation applies; verify specific RoHS/REACH/UL declarations with the manufacturer or your Siemens channel partner."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-1KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-1KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}