{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-3KK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-3KK06","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-3KK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-3KK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, Super resistant K design, 2-pole, 6 A, 30 mA, Type F, B characteristic, 6 kA per EN 60898, 1 MW.","salesMarkdown":"The Siemens 5SV1316-3KK06 is a SENTRON RCBO — residual current operated circuit breaker with integral overcurrent protection — in the Super resistant K design, meaning the housing and internal construction are specified for environments with higher chemical or thermal stress than standard residential RCBOs. It carries a 6 A rated current (B curve) and a 30 mA residual current trip threshold, Type F, which means it detects AC pulsating and smooth DC residual currents plus high-frequency AC components from variable-speed drives or LED drivers. The 2-pole device occupies a single modular width (18 mm) on the DIN rail, with supply feed accepted from either top or bottom and any mounting position allowed. ## Temperature derating — the real current rating The 6 A rating holds only at 30 °C ambient. At 40 °C the continuous current drops to 5.64 A; at 50 °C it is 5.28 A; at 60 °C it is 4.86 A; at 70 °C it is 4.44 A. If the panel internal temperature runs above 30 °C — common in crowded enclosures or near transformers — size the upstream protective device and the downstream load against the derated figure, not the nameplate 6 A. ## Mounting and environment Snap-on DIN rail mount, 18 mm width (1 MW). Halogen-free and silicon-free construction, which matters for clean-room or high-reliability installations where outgassing can contaminate contacts or optics. Touch protection is integral on the terminals.","metaTitle":"Siemens 5SV1316-3KK06 SENTRON RCBO, 6 A, 30 mA, Type F, B Cu","metaDescription":"Siemens 5SV1316-3KK06 SENTRON RCBO, 6 A rated, 30 mA residual current, Type F, B characteristic, 6 kA breaking capacity. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"77 mm","Poles":"2","Width":"18 mm","Height":"90 mm","Product Status":"Active","Energy Limitation Class":"3"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027028&mlfb=5SV1316-3KK06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV1316-3KK06/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-3KK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-3KK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}