{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-3KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-3KK16","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-3KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-3KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, super resistant K design, B-curve 16 A, 1P+N, 6 kA (EN 60898) / 15 kA (IEC 60947-2), 1 MW wide, IP20.","salesMarkdown":"Siemens 5SV1316-3KK16 is a SENTRON RCBO in super resistant K design, B-curve, 1P+N, 18 mm wide, 1 MW. At 40 °C it derates to 15.2 A, at 50 °C to 14.4 A, and at 70 °C to 12.8 A. That's a 20 % drop from the nominal at the top of the operating range. At 18 mm wide (1 MW) and 77 mm deep, it occupies a single modular slot on a standard DIN rail. IP20 rated with conductors connected — that's the usual protection for inside a distribution board; no special sealing required.","metaTitle":"Siemens 5SV1316-3KK16 SENTRON RCBO, B-16A, 6kA/15kA, 1P+N, 1","metaDescription":"Siemens 5SV1316-3KK16 SENTRON RCBO, B-curve 16A, 6kA (EN 60898) / 15kA (IEC 60947-2), 1P+N, 1MW wide, super resistant K design, IP20. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1316-3KK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 6 kA type F 30 mA B16","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Super resistant K","Weight With Packaging":"133 g","at 30 °C rated value":"16 A","at 40 °C rated value":"15.2 A","at 45 °C rated value":"14.88 A","at 50 °C rated value":"14.4 A","at 55 °C rated value":"14.08 A","at 60 °C rated value":"13.6 A","at 65 °C rated value":"13.28 A","at 70 °C rated value":"12.8 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"15 kA","Surge Current Resistance At (8/20) μS":"3 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027031&mlfb=5SV1316-3KK16"},"ai":{"faq":[{"question":"What is 5SV1316-3KK16's listed depth?","answer":"The depth is 77 mm, with an installation depth of 70 mm."},{"question":"What is 5SV1316-3KK16's listed width?","answer":"The width is 18 mm, which is 1 modular width unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-3KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-3KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}