{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-4KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-4KK16","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-4KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-4KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, super resistant K design, 1P+N, C16, 30 mA, type F, 6 kA (EN 60898) / 10 kA (IEC 60947-2), 1 MW, 18 mm wide.","salesMarkdown":"It protects one phase and the neutral conductor, rated at C16 with 30 mA earth leakage sensitivity and type F characteristic for frequency-sensitive loads like variable-speed drives or pumps. The C tripping characteristic handles moderate inrush — think motor starters, lighting banks, or small transformer loads — without nuisance trips, while still clearing fast on hard faults. Type F is the key here: it's designed for circuits with frequency converters or drives that can inject mixed-frequency leakage currents. Standard AC or A type RCDs can desensitize on those waveforms; type F maintains trip integrity up to 1 kHz. At 30 mA sensitivity, it covers personnel protection (additional protection per IEC 60364) and equipment ground-fault detection. The 1P+N pole configuration switches the phase and monitors neutral current for the residual current function, but does not switch the neutral — it's a switched-neutral design for the RCD sense, not a full 2-pole disconnect. At 18 mm wide (1 MW), it fits standard DIN-rail enclosures and leaves room for adjacent breakers or auxiliaries in a crowded panel.","metaTitle":"Siemens 5SV1316-4KK16 SENTRON RCBO, 1P+N C16 30mA Type F","metaDescription":"Siemens SENTRON 5SV1316-4KK16 RCBO, 1P+N, C16, 30 mA, type F. 6 kA (EN 60898) / 10 kA (IEC 60947-2). Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1316-4KK16","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 6 kA type F 30 mA C16","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Super resistant K","Weight With Packaging":"133 g","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"10 kA","Surge Current Resistance At (8/20) μS":"3 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027035&mlfb=5SV1316-4KK16"},"ai":{"faq":[{"question":"What is the difference between 5SV1316-4KK16 and 5SY4116-7CV?","answer":"The 5SY4116-7CV is a 1-pole MCB only (no RCD), rated 15 kA per IEC 60947-2. The 5SV1316-4KK16 is a 1P+N RCBO combining overcurrent and 30 mA residual current protection, with 10 kA per IEC 60947-2. They share the same 18 mm width and 90 mm height, so the RCBO will fit a panel designed for the MCB, but you gain the earth leakage function in the same footprint."},{"question":"Where can I buy 5SV1316-4KK16 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does this RCBO carry?","answer":"It is rated per EN 60898 (6 kA) and IEC 60947-2 (10 kA), halogen-free and silicon-free, with overvoltage category III and pollution degree 2. The SENTRON brand provides standard declaration of conformity and CE marking for EU markets."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-4KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-4KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}