{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-6KK13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-6KK13","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-6KK13","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-6KK13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1316-6KK13 RCBO, 1P+N, Type B, 13 A rated at 30 °C, 6 kA per EN 60898, 15 kA per IEC 60947-2, 18 mm wide, 77 mm deep. Halogen-free design.","salesMarkdown":"## Temperature derating matters in warm panels The 5SV1316-6KK13: Ratings drop from 13 A at 30 °C to 10.01 A at 70 °C. If your cabinet runs hot, factor the published derating curve—don't rely on the 30 °C figure alone. At a typical 40 °C inside a panel, the part carries 12.35 A; at 50 °C it's 11.57 A. ## Compact 18 mm footprint, any mounting position 18 mm wide (1 modular unit) and 77 mm deep, installation depth of 70 mm. IP20 with connected conductors and installed distribution board. ## Active production, no obsolescence concern Lifecycle stage marked as current. This RCBO is in ongoing manufacture; no last-time-buy window or substitute search needed for new BOM lines. ## What this RCBO is—and isn't The 5SL4363-7 and 5SY6350-7 peers are standard MCBs—without residual current protection. Swapping an MCB into a slot designed for an RCBO means losing the RCD function and likely breaking selectivity. Keep each part in its intended role. ## Sourcing note Available to order against an RFQ. Halogen-free and silicon-free construction.","metaTitle":"Siemens 5SV1316-6KK13 SENTRON RCBO, Type B 13A 6kA","metaDescription":"Current production SENTRON RCBO, 1P+N, 13A at 30°C, 6kA IEC 60898 / 15kA IEC 60947-2, 18mm wide, 77mm deep. Halogen-free. Active lifecycle.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1316-6KK13","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 6 kA type A 30 mA B13","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"13 A","at 40 °C rated value":"12.35 A","at 45 °C rated value":"11.96 A","at 50 °C rated value":"11.57 A","at 55 °C rated value":"11.18 A","at 60 °C rated value":"10.79 A","at 65 °C rated value":"10.4 A","at 70 °C rated value":"10.01 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"B","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"15 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$301.92","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027038&mlfb=5SV1316-6KK13"},"ai":{"faq":[{"question":"Can the 5SV1316-6KK13 replace a 5SL4363-7 MCB?","answer":"No. The 5SV1316-6KK13 is an RCBO combining overcurrent and residual current protection. The 5SL4363-7 is a standard MCB without RCD. Wiring and function differ; swapping one for the other would lose residual current protection."},{"question":"What compliance documentation is available for this part?","answer":"The part is halogen-free and silicon-free, constructed for overvoltage category III and pollution degree 2. It carries IP20 protection when installed in a distribution board with conductors connected. Specific RoHS or UL certifications are not listed in the provided data."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-6KK13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-6KK13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}