{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-6LK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-6LK06","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-6LK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-6LK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1316-6LK06, RCBO, 2-pole (1 protected), rated current 6 A, tripping characteristic B, residual current Type A, 30 mA, breaking capacity 6 kA acc. to EN 60898 / 35 kA acc. to IEC 60947-2, width 18 mm (1 MWU).","salesMarkdown":"## What it is and what it does The Siemens 5SV1316-6LK06 is a 2-pole RCBO (residual current circuit breaker with overcurrent protection) from the SENTRON family, combining a B-curve MCB and a Type A RCD in a single 18 mm wide module. It protects a single pole against overload and short-circuit (B characteristic, 6 A rated) while the 30 mA Type A residual current unit detects sinusoidal AC and pulsating DC fault currents. The second pole is switched but not protected — a common arrangement for single-phase circuits where the neutral is switched. Rated breaking capacity is 6 kA per EN 60898 (the domestic-standard test) and 35 kA per IEC 60947-2 (the industrial-standard test). The higher 35 kA figure means it can interrupt faults up to that level without welding contacts or cascading failure upstream — relevant when the device sits in an industrial panel with high prospective fault current. The device is rated for overvoltage category III and pollution degree 2, which covers fixed-installation distribution boards in typical industrial and commercial environments. Touch protection is built in, and the IP20 rating applies once the distribution board is installed with connected conductors. ## Thermal derating and mounting The 6 A nominal rating holds at 30 °C ambient. Above that, the thermal-magnetic trip element derates linearly: 5.64 A at 40 °C, 5.28 A at 50 °C, 4.86 A at 60 °C, and 4.44 A at 70 °C. If the panel ambient runs hot, size the circuit for the derated value — the trip curve shifts, not the protection logic. Mounting position is unrestricted (any orientation), and the unit occupies one modular width unit (18 mm) on a DIN rail. Supply can enter from either top or bottom. Installation depth is 70 mm behind the panel face; overall depth is 77 mm including the front projection.","metaTitle":"Siemens 5SV1316-6LK06 SENTRON RCBO, 6A B-curve, 30mA Type A,","metaDescription":"Siemens 5SV1316-6LK06 SENTRON RCBO, 6 A rated, B characteristic, 30 mA Type A residual current, 2-pole (1 protected). Breaking capacity 6 kA (EN 60898) / 35 kA (IEC 60947-2). Curre","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","acc. to IEC 81346-2":"F","at AC / rated value":"6 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Short-time delayed G, super resistant K","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"133 g","at 30 °C / rated value":"6 A","at 40 °C / rated value":"5.64 A","at 45 °C / rated value":"5.46 A","at 50 °C / rated value":"5.28 A","at 55 °C / rated value":"5.04 A","at 60 °C / rated value":"4.86 A","at 65 °C / rated value":"4.62 A","at 70 °C / rated value":"4.44 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"35 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"253 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"3 kA","Type Of Voltage / Of The Operating Voltage":"AC","Product Component / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027040&mlfb=5SV1316-6LK06","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV1316-6LK06/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV1316-6LK06?","answer":"6 kA per EN 60898 and 35 kA per IEC 60947-2. The higher figure applies in industrial panels where fault current can exceed domestic levels."},{"question":"What is the residual current type and sensitivity?","answer":"Type A (sinusoidal AC and pulsating DC) at 30 mA sensitivity."},{"question":"What is the tripping characteristic and rated current?","answer":"B characteristic (3–5 In magnetic trip) at 6 A rated current, derated above 30 °C ambient."},{"question":"Where can I buy 5SV1316-6LK06?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-6LK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-6LK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}