{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-7GV13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-7GV13","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-7GV13","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7GV13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1316-7GV13 RCBO, 2-pole 1P+N, 230 V AC, 13 A rated current, tripping characteristic C, 6 kA breaking capacity per EN 60898, Type A fault current, instantaneous design, halogen-free, silicon-free, IP20.","salesMarkdown":"The Siemens SENTRON 5SV1316-7GV13 is a 2-pole RCBO (residual current circuit breaker with overcurrent protection) in a 1P+N configuration, rated for 230 V AC at 50 Hz. The Type A fault current detection means it handles pulsating DC residual currents from single-phase rectifiers, common in modern electronics loads. Rated current drops with ambient temperature: 12.35 A at 40 °C, 11.57 A at 50 °C, and 10.01 A at 70 °C. Mounting position is unrestricted. Feed from top or bottom — no orientation constraint. IP20 with the distribution board installed and conductors connected.","metaTitle":"Siemens 5SV1316-7GV13 SENTRON RCBO, 2-pole 13A C-curve 6kA","metaDescription":"Siemens SENTRON 5SV1316-7GV13 RCBO, 2-pole 1P+N, 230V AC, 13A rated current, C-curve, 6kA breaking capacity per EN 60898. Type A fault current, halogen-free, silicon-free. Active p","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","at 30 Cel":"13 A","at 40 Cel":"12.35 A","at 45 Cel":"11.96 A","at 50 Cel":"11.57 A","at 55 Cel":"11.18 A","at 60 Cel":"10.79 A","at 65 Cel":"10.4 A","at 70 Cel":"10.01 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","Type Of Voltage":"AC","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","at AC / rated value":"230 V","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Energy Limiting Class":"3","Number Of Width Units":"1","Type Of Fault Current":"A","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SV1","Tripping Characteristic Class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"10 kA","Product Feature / Touch Protection":"Yes","Supply Voltage Frequency / Rated Value":"50 Hz","Tripping Residual Current / Rated Value":"30 mA","operating current / at AC / rated value":"13 A","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"1 kA","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1361426&mlfb=5SV1316-7GV13","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7GV13/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SV1316-7GV13 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the thermal derating for 5SV1316-7GV13?","answer":"Rated current is 13 A at 30 °C, derating to 12.35 A at 40 °C, 11.57 A at 50 °C, and 10.01 A at 70 °C."},{"question":"What compliance documentation does this RCBO carry?","answer":"Rated per EN 60898 for breaking capacity, halogen-free and silicon-free. Overvoltage category III, pollution degree 2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-7GV13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-7GV13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}