{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-7KK02","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-7KK02","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-7KK02","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7KK02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, Type C, 2 A, 1P+N, 6 kA (EN 60898) / 10 kA (IEC 60947-2), 18 mm width, 50 Hz, IP20.","salesMarkdown":"Rated 2 A at 30 °C ambient with a C tripping characteristic (magnetic release between 5× and 10× In), it handles resistive and moderate motor-start loads on 230 V AC, 50 Hz circuits. Thermal derating is published across the full ambient range: 1.9 A at 40 °C, 1.8 A at 50 °C, 1.7 A at 60 °C, and 1.6 A at 70 °C. Installation depth is 70 mm plus the 77 mm overall depth — plan gland-plate clearance accordingly. Surge voltage withstand is 4 kV.","metaTitle":"Siemens SENTRON 5SV1316-7KK02 RCBO, 2A C-curve, 1P+N, 6kA EN","metaDescription":"Siemens SENTRON 5SV1316-7KK02 RCBO, 2A rated, C tripping curve, 1P+N, 6 kA per EN 60898 / 10 kA per IEC 60947-2. 18 mm wide, IP20. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"2 A","at 40 °C rated value":"1.9 A","at 45 °C rated value":"1.86 A","at 50 °C rated value":"1.8 A","at 55 °C rated value":"1.76 A","at 60 °C rated value":"1.7 A","at 65 °C rated value":"1.66 A","at 70 °C rated value":"1.6 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"10 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027048&mlfb=5SV1316-7KK02","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7KK02/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV1316-7KK02?","answer":"6 kA per EN 60898 and 10 kA per IEC 60947-2. The higher figure applies when the device is used as a distribution-circuit breaker under the industrial standard."},{"question":"What is the width of 5SV1316-7KK02?","answer":"18 mm, which is one modular-width unit on a standard DIN-rail panel."},{"question":"Where can I buy 5SV1316-7KK02?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-7KK02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-7KK02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}