{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-7KK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-7KK10","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-7KK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7KK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO compact, 1P+N, 6 kA, type A, 30 mA, C10, instantaneous design.","salesMarkdown":"It carries a C10 tripping characteristic (10 A rated current, magnetic trip at 5–10× In) and a 30 mA type A residual-current element, making it suitable for protecting final circuits against both overload/short-circuit and sinusoidal/pulsating DC fault currents. The instantaneous design (no intentional time delay on the RCD side) means it trips within 40 ms on a residual fault — standard for socket-outlet circuits where fast disconnection is required. The 1-module width (18 mm) saves one slot compared to a 2-module RCBO — useful when packing multiple circuits into a tight enclosure. Rated insulation voltage 253 V, surge voltage resistance 4 000 V, and surge current withstand 1 kA (8/20 µs) — the MOV or gas-discharge coordination is built into the device, so no external surge arrester is required for typical residential/commercial service entrance coordination.","metaTitle":"Siemens SENTRON 5SV1316-7KK10 RCBO, 1P+N, C10, 30 mA, 6 kA","metaDescription":"Active-production Siemens SENTRON RCBO, 1P+N, type A, 30 mA, C10 characteristic, 6 kA per EN 60898, 10 kA per IEC 60947-2. 18 mm wide, halogen-free. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1316-7KK10","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 6 kA type A 30 mA C10","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"10 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$112.65","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027051&mlfb=5SV1316-7KK10"},"ai":{"faq":[{"question":"What is the breaking capacity of this RCBO?","answer":"6 kA per EN 60898 and 10 kA per IEC 60947-2. The higher IEC figure applies when the device is used in industrial applications under the coordination rules of that standard."},{"question":"What is the width and depth of 5SV1316-7KK10?","answer":"Width 18 mm (1 modular unit), depth 77 mm, installation depth 70 mm. Fits standard SENTRON distribution boards."},{"question":"Does it replace a standard MCB + RCCB combination?","answer":"Yes — the RCBO combines overcurrent protection (C10 curve) and residual-current protection (30 mA type A) in one 1-module device, saving panel space compared to a separate MCB and RCCB."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-7KK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-7KK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}