{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-7KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-7KK16","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-7KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SV1316-7KK16, 1P+N, C-curve 16 A, breaking capacity 6 kA (EN 60898) / 10 kA (IEC 60947-2), 50 Hz, 18 mm wide, IP20.","salesMarkdown":"It protects a single-phase final subcircuit against overload, short-circuit, and earth leakage. The 1P+N design means it switches the live pole and monitors the neutral; the neutral is not switched but is monitored for imbalance. Thermal derating: 15.2 A at 40 °C, down to 12.32 A at 70 °C. One modular width (18 mm) means it occupies a single slot in a distribution board. Any mounting position is allowed, so it works in horizontal busbar or vertical DIN-rail layouts. IP20 with connected conductors; the enclosure must be part of a distribution board to maintain the rating. ## How it compares to a common sibling The 5SL6120-7 is a straight MCB (no RCD) in the same SENTRON family, same 1-module width, same C-curve. The 5SV1316-7KK16 adds the residual-current block inside the same footprint — you get earth-leakage protection without giving up a slot. If your BOM already uses the 5SL6120-7 and you need to add RCD protection to that circuit, this RCBO drops into the same panel layout; no rewiring of the busbar position is required, but you do need to connect the neutral through the device. The 5SV1316-7KK16 is the combined solution where the 5SL6120-7 is the breaker-only alternative.","metaTitle":"Siemens 5SV1316-7KK16 SENTRON RCBO, 16A C-curve, 6/10kA, 1P+","metaDescription":"Siemens SENTRON 5SV1316-7KK16 RCBO, 16A rated, C-curve, 6kA (EN 60898) / 10kA (IEC 60947-2), 1P+N, 2-pole, 18mm wide, halogen-free. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Weight With Packaging":"133 g","at 30 °C rated value":"16 A","at 40 °C rated value":"15.2 A","at 45 °C rated value":"14.72 A","at 50 °C rated value":"14.24 A","at 55 °C rated value":"13.76 A","at 60 °C rated value":"13.28 A","at 65 °C rated value":"12.8 A","at 70 °C rated value":"12.32 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"10 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027053&mlfb=5SV1316-7KK16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7KK16/alternatives.json"},"ai":{"faq":[{"question":"Will 5SV1316-7KK16 drop into a panel specified around 5SL6120-7 without rewiring?","answer":"Yes, both are 1-module wide (18 mm) SENTRON devices on standard DIN rail, so the mechanical fit is identical. The 5SV1316-7KK16 adds residual-current protection, which requires connecting the neutral through the device — the 5SL6120-7 does not. No busbar repositioning is needed, but the neutral wire must be routed through the RCBO."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-7KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-7KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}